NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan April 15, 2002 Indoor Air Quality Assessment Page 3 H.S. of Economics and Finance fM833) ATC Project No. 15-19125-0291

Real-Time Environmental Measur^ents

ATC collected thirty-nine (39) sets of real-time environmental measurements consisting of thirty-five (35) in the school building and four (4) outdoors. Field data sheets are found in the Attachment. Readings began at 11:45 A.M. and concluded after 1:21 P.M. The results are described below.

Temperature

Indoor dry bulb temperature measurements ranged from 58.2 °F to 77.8 °F. Four (4) of the indoor measurements for temperature were above, and four (4) measurements were bellow and twenty-eight (28) measurements were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature ranged from 52.2 to 58.9 °F.

Relative Humidity

The relative humidity indoors ranged from 27.8 percent to 39.0 percent. Three (3) of the indoor measurements for relative humidity were below and thirty-two (32) were within the ASHRAE recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 31.0 to 33.0 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 385 ppm to 1021 ppm. All of the indoor measurements for CO2 were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 422 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1142 ppm (background level -1- 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Cqrbon^onmddeCpncentrqtipn

Carbon monoxide concentrations indoors were between 1 to 3 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration ranged from 2 ppm to 3 ppm.

Respirable Particulates (PM2,5)

Respirable particulate concentrations* indoors ranged between 6 pg/m^ to 42 pg/m^ with an average 13 pg/m^- None of the indoor measurements were above the NPAAQS of 65 pg/m^ 24- hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and one (1) Indoor Measurement was above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentration ranged from 16 pg/m^ to 42 pg/m^ with an average of 31 pg/m^. None of the outdoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Two (2) of the four (4)

C11X_21]:iC10 0_0 02819 822

NYC-WTC_000383086

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000383086Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000402451

ATC IAQ measurements report for High School of Economics and Finance, 100 Trinity Place, 2002.

Similar indexed content

NYC-WTC_000259145

Report of IAQ measurements at 100 Trinity Place for BOE program, March 2002.

Similar indexed content

Compare copies and versions →