Mr. Bernard P. Orlan April 16, 2002 Indoor Air Quality Assessment Page 3 H.S. of Economics and Finance (M833) ATC Project No. 15-19125-0291

Real-Time Environmental Measurements

ATC collected ninety-four (94) sets of real-time environmental measurements consisting of eighty-two (82) inside the school building and twelve (12) outdoors. Field data sheets are found in the Attachment. Readings began at 9:15 A.M. and concluded after 5:00 P.M. The results are described below.

Temperature

Indoor dry bulb temperature measurements ranged from 59.1 °F to 79.3 °F. One (I) of the indoor measurements for temperature was below, eighty (80) measurements were above, and one (1) measurement was within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature ranged from 77.6 to 79.3 °F.

Relative Humidity

The relative humidity indoors ranged from 43.6 percent to 62.1 percent. Two (2) of the indoor measurements for relative humidity were above and eight (80) were within the ASHRAE recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 44.9 to 52.9 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 411 ppm to 1302 ppm. All of the indoor measurements for CO2 were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO? concentration was 639 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1339 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 2 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were also 2 ppm for all readings.

Respirable Particulates (PM2,5)

Respirable particulate concentrations* indoors ranged between 6 pg/m^ to 19 pg/m^ with an average 12 pg/m^- All of the indoor and outdoor measurements for respirable particulates were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentration ranged from 11 pg/m- to 18 pg/m^ with an average of 14 pg/m^.

CITY_21MC100_002900263

NYC-WTC_000404487

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000404487Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000223588

Report of indoor air quality measurements collected at the High School of Economics and Finance on May 23, 2002.

Similar indexed content

Compare copies and versions →