Indoor air quality measurements collected March 19, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗Indoor air quality measurements collected at HS Economics & Finance for BOE program.
NYC-WTC_000384236–000384240OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan March 20, 2002 Indoor Air Quality Assessment Page 3 H.S. of Economics and Finance (M833) ATC Project No. 15-19125-0291 Real-Time Environmental Measurements
ATC collected one hundred (100) sets of real-time environmental measurements consisting of eighty-eight (88) in the school building and twelve (12) outdoors. Field data sheets are found in the Attachment. Readings began at 10:36 A.M. and concluded after 4:55 P.M. The results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 66.3 °F to 77.4 °F. Four (4) of the indoor measurements for temperature were below and twenty-nine (29) were above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature ranged from 43.8 to 45.8 °F.
Relative Humidity
The relative humidity indoors ranged from 26.9 percent to 47.3 percent. Twenty-four (24) of the indoor measurements for relative humidity were below and sixty-four (64) are within the ASHRAE recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 27.3 to 47.4 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 449 ppm to 1293 ppm. Two (2) of the indoor measurements for CO2 were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 483 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1183 ppm (background level + 700 ppm). The highest reading (1293 ppm) was measured in room 705 approximately at 11:02 AM with 31 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were between 0 to 3 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration ranged from 3 to 4 ppm.
Respirable Particulates (PM2,3)
Respirable particulate concentrations* indoors ranged between 3 pg/m^ to 37 pg/m^ with an average 11 pg/m^- All of the indoor measurements were below the NPAAQS of 65 pg/m^ 24- hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. None of the eight-eight (88) instantaneous indoor readings were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentration ranged from 27 pg/m^ to 86 pg/m^ with an average of 59 pg/m3. Five (5) of the outdoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter.
CITY_2IMCl0 0_0 0 0 4 6 7 9 2 7 NYC-WTC_000384238
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000402524
Indoor air quality measurements collected March 19, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384192
IAQ measurements collected March 14, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000179980
Letter from ATC Associates reporting indoor air quality measurements collected at a school on March 14, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402480
Indoor air quality measurements collected on March 14, 2002 for the specified school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384177
IAQ measurements collected March 13, 2002 at High School of Economics and Finance.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000404462
IAQ measurements at HS of Economics and Finance, April 8, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402495
Indoor air quality measurements collected on March 15, 2002 for the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402465
Indoor air quality measurements collected at the referenced school in March 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000219378
ATC Associates report on indoor air quality measurements collected at the High School of Economics and Finance on April 8, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384207
Indoor air quality measurements at HS of Economics & Finance for BOE, March 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402533
Indoor air quality measurements collected March 21, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259161
Indoor air quality data collection at Trinity Place site, April 2002.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000402524
Indoor air quality measurements collected March 19, 2002 at the referenced school.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402465
Indoor air quality measurements collected at the referenced school in March 2002.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384192
IAQ measurements collected March 14, 2002 at the referenced school.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402391
IAQ report for High School of Economics and Finance based on measurements collected Mar 4, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259006
IAQ measurements at H.S. of Economics and Finance; scope of work (Mar 2002).
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000404485
IAQ measurement report for High School of Economics and Finance (M833) dated Apr 15, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
Indoor air quality measurements collected March 19, 2002 at the referenced school.
Similar indexed content
NYC-WTC_000384192
IAQ measurements collected March 14, 2002 at the referenced school.
Similar indexed content
Letter from ATC Associates reporting indoor air quality measurements collected at a school on March 14, 2002.
Similar indexed content
Indoor air quality measurements collected on March 14, 2002 for the specified school.
Similar indexed content
NYC-WTC_000384177
IAQ measurements collected March 13, 2002 at High School of Economics and Finance.
Similar indexed content