Mr. Bernard P. Orlan March 5, 2002 Indoor Air Quality Assessment Page 3 H.S. of Economics and Finance (M833) ATC Project No. 15-19125-0291
Real-Time Environmental Measurements
ATC collected one hundred (100) sets of real-time environmental measurements consisting of eighty-five (85) in the school building and fifteen (15) outdoors. Field data sheets are found in the Attachment. Readings began at 11:30 A.M. and concluded after 5:48 P.M. The results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 56.9 °F to 79.6 °F. Fourteen (14) of the indoor measurements were below and thirty-seven (37) were above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature ranged from 39.2 to 49.4 °F.
Relative Humidity
The relative humidity indoors ranged from 16.8 percent to 44.3 percent. Fifty-six (56) measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. All other measurements were within the ASHRAE recommended range. The outdoor relative humidity ranged from 17.8 to 25.7 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 513 ppm to 1271 ppm. Eighty-four (84) of the indoor measurements were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 510 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1210 ppm (background level + 700 ppm). One highest reading (1271 ppm) was measured in room 705 at 11:27 AM with 31 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 1 to 5 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration ranged from 1 to 4 ppm.
Respirable Particulates (PM2,5)
Respirable particulate concentrations* indoors ranged between 0 pg/m^ to 23 pg/m^ with an average 6 pg/m^- None of the measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The PM2.5 average concentration was also below the USEPA recommended concentration of 40 pg/m^ for sensitive individuals / children. The outdoor respirable particulate concentration ranged from 29 pg/m^ to 84 pg/m^ with an average of 47 ug/m^.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.
CITY_21MC100_002924109
NYC-WTC_000402393
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000259006
IAQ measurements at H.S. of Economics and Finance; scope of work (Mar 2002).
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402387
Indoor air quality IAQ report for High School of Economics and Finance, measurements on Mar 1, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259002
ATC report of IAQ measurements at High School of Economics and Finance (Feb 2002).
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259010
IAQ measurements conducted March 5, 2002 at H.S. of Economics and Finance (M833).
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000404489
IAQ measurements conducted at the referenced school as part of BOE program (Apr 16, 2002).
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000179968
Letter from ATC Associates reporting indoor air quality measurements collected at a school on March 1, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402395
IAQ measurements at the referenced school as part of BOE program, collected Mar 5, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396659
IAQ report for measurements collected May 28, 2002 under BOE program.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000383143
IAQ measurements collected April 23, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000383111
IAQ measurements collected April 18, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000383107
Indoor air measurements collected April 17, 2002 at the referenced school.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259222
IAQ measurements at the referenced school; BOE-ordered.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000259006
IAQ measurements at H.S. of Economics and Finance; scope of work (Mar 2002).
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402395
IAQ measurements at the referenced school as part of BOE program, collected Mar 5, 2002.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402524
Indoor air quality measurements collected March 19, 2002 at the referenced school.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259010
IAQ measurements conducted March 5, 2002 at H.S. of Economics and Finance (M833).
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384236
Indoor air quality measurements collected at HS Economics & Finance for BOE program.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402387
Indoor air quality IAQ report for High School of Economics and Finance, measurements on Mar 1, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000259006
IAQ measurements at H.S. of Economics and Finance; scope of work (Mar 2002).
Similar indexed content
NYC-WTC_000402387
Indoor air quality IAQ report for High School of Economics and Finance, measurements on Mar 1, 2002.
Similar indexed content
NYC-WTC_000259002
ATC report of IAQ measurements at High School of Economics and Finance (Feb 2002).
Similar indexed content
NYC-WTC_000259010
IAQ measurements conducted March 5, 2002 at H.S. of Economics and Finance (M833).
Similar indexed content
NYC-WTC_000404489
IAQ measurements conducted at the referenced school as part of BOE program (Apr 16, 2002).
Similar indexed content