Mr. Bernard P. Orlan March 6, 2002
Indoor Air Quality Assessment Page 3
H.S. of Economics and Finance (M833) ATC Project No. 15-19125-0291
Real-Time Environmental Measurements
ATC collected one hundred (100) sets of real-time environmental measurements consisting of
eighty-eight (88) in the school building and twelve (12) outdoors. Field data sheets are found in
the Attachment. Readings began at 11:15 A.M. and concluded after 4:55 P.M. The results are
described below.
Temperature
Indoor dry bulb temperature measurements ranged from 48.5 °F to 78.6 °F. Twenty-nine (29) of
the indoor measurements were below and seventeen (17) were above the range of 68 to 75°F (at
50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating
season (wintertime conditions). The outdoor temperature ranged from 36.6 to 49.5 °F.
Relative Humidity
The relative humidity indoors ranged from 15.4 percent to 36.2 percent. Seventy-four (74)
measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant
comfort. Fourteen (14) measurements were within the ASHRAE recommended range. The
outdoor relative humidity ranged from 14.2 to 22.9 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 347 ppm to 1673 ppm. Five (5) of the
indoor measurements were above the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The outdoor (background) CO2
concentration was 707 ppm. Therefore, the maximum acceptable level of CO2 at this location
was 1407 ppm (background level + 700 ppm). The highest reading (1673 ppm) was measured in
stairwell B at 12:00 PM. Levels above the recommended maximum do not indicate a health risk.
Carbon dioxide measurements are used as an indicator of available outdoor air. The primary
source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 1 to 3 ppm. These concentrations were below the
NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration ranged from 1 to 5 ppm.
Respirable Particulates (PM2^5)
Respirable particulate concentrations* indoors ranged between 0 pg/m^ to 60 pg/m^ with an
average 12 pg/m^- None of the measurements were above the NPAAQS of 65 pg/m^ 24-hour
average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter.
The PM2 5 average concentration was also below the USEPA recommended concentration of 40
pg/m^ for sensitive individuals / children. The outdoor respirable particulate concentration
ranged from 21 pg/m^ to 52 pg/m^ with an average of 30 ug/m^.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.