Mr. Bernard P. Orlan March 6,2002
Indoor Air Quality Assessment Page 4
H.S. of Economics and Finance fM833) ATC Project No. 15-19125-0291
TVOC Concentration
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC
concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• The interior of the building appeared clean and tree of dust and debris;
• The building was occupied at the time of the assessment;
• No smoke odor was detected in the building;
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of respirable particulates, CO, and TVOCs were below applicable standards
and guidelines.
2. Seventy-four (74) indoor measurements for relative humidity were below and fourteen (14)
were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort.
3. Twenty-nine (29) indoor temperature measurements were below and seventeen (17) were
above the range of 68 to 75°F (at 50 percent relative humidity recommended by ASHRAE
Standard 55-1992 during the heating season (wintertime conditions).
4. Five (5) of the indoor measurements for carbon dioxide were above the ASEIRAE Standard
62-1999 recommended maximum concentration of <700 ppm above the background level.
The highest reading was measured in stairwell B at 12:00 PM.
It is our pleasure to provide these indoor air quality services to the New York City Board of
Education. If you have any questions about this report, please call (212) 353-8280, extension
336 or 212.
Sincerely,
A TCASSOCIA TES INC.
Reviewed by:
James R. Cohn, CIH, CSP
Senior Pro ect Manager Regional Manager
Industrial Hygiene Division
Attachment