Mr. Bernard P. Orlan Apnl 15,2002 Indoor Air Quality Assessment Page 2 H.S. of Economics and Finance (M833) ATC Project No. 15-19125-0291
The results of the sampling represent conditions found on the dates of the survey and may not represent conditions found at other times. The information presented in this report should be used by the BOE as a guide to assess the need for further improvements in current indoor air quality control activities.
EVALUATION CRITERIA
Currently, there are no regulatory standards for indoor air quality in non-industrial buildings, such as offices and schools. For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications:
Ventilation for Acceptable Indoor Air Quality (ASHRAE 62-J999), American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE); Thermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992); Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA).
Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation. Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality will be achieved at all times.
TABLE 1 TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED
PARAMETER TARGET LEVEL AGENCY OR ORGANIZATION Carbon Dioxide <700 parts per million (ppm) ASHRAE 62 (CQ2)___________ above background level Carbon Monoxide 9 ppm ASHRAE 62 (adopted from (CO) USEPA NPAAQS) Respirable 65 micrograms per cubic meter USEPA NPAAQS Particulates (PM2 5) of air (pg/m^) 24-hour average 40 pg/m^ 24-hour average USEPA - Recommendation for children / sensitive individuals Temperature Summer: 73-79°F at 50% RH ASHRAE 55 Winter: 68-75°F at 50% RH Relative Humidity 30 - 60 % ASHRAE55 Total Volatile Organic Compounds 1 ppm AIHA (TVOC) USEPA = United States Environmental Protection Agency NPAAQS = National Primary Ambient-Air Quality Standard AIHA = American Industrial Hygiene Association
CITY_21MC100_002879821
NYC-WTC_000383085
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000402451
ATC IAQ measurements report for High School of Economics and Finance, 100 Trinity Place, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402542
Indoor air quality measurements collected March 25, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402538
Indoor air quality measurements collected March 22, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384250
Chain-of-custody for potable water sampling at Trinity Place site, March 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259145
Report of IAQ measurements at 100 Trinity Place for BOE program, March 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000383080
IAQ measurements conducted April 11, 2002 for BOE at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384246
Indoor air quality measurements collected on March 22, 2002 at HS Economics & Finance.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396436
May 3, 2002 IAQ measurements for BOE at HSEF (M833).
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000383115
IAQ measurements collected April 19, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402437
IAQ measurements conducted March 11, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384163
IAQ report covering measurements and signatures for school site.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000383088
IAQ measurements at High School of Economics and Finance conducted April 15, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000402395
IAQ measurements at the referenced school as part of BOE program, collected Mar 5, 2002.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000383193
IAQ measurements collected April 29, 2002 for BOE at the referenced school.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000219394
ATC Associates report on indoor air quality measurements collected at the High School of Economics and Finance on April 24, 2002.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000383092
IAQ measurements collected April 16, 2002 for BOE evaluation at the referenced school.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000383062
Indoor air quality measurements at H.S. [name], Apr 2002.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402423
Indoor air quality measurements collected on March 8, 2002 at the referenced school.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
ATC IAQ measurements report for High School of Economics and Finance, 100 Trinity Place, 2002.
Similar indexed content
NYC-WTC_000402542
Indoor air quality measurements collected March 25, 2002 at the referenced school.
Similar indexed content
NYC-WTC_000402538
Indoor air quality measurements collected March 22, 2002 at the referenced school.
Similar indexed content
NYC-WTC_000384250
Chain-of-custody for potable water sampling at Trinity Place site, March 2002.
Similar indexed content
Report of IAQ measurements at 100 Trinity Place for BOE program, March 2002.
Similar indexed content