Mr. Bernard P. Orlan March 8, 2002 Indoor Air Quality Assessment Page 3 H.S. for Leadership & Public Service (M894) ATC Project No. 15-19125-0290 Real-Time Environmental Measurements I ATC collected one hundred and forty (140) sets of real-time environmental measurements consisting of one hundred and twenty-eight (128) in the school building and twelve (12) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings began at 10:23 A.M. and concluded after 6:23 P.M. The results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 67.8 °F to 77.2 °F. One (1) indoor measurement was below and four (4) measurements were above the range of 68 to 75 °F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature range was 55.6 °F to 64.7 °F.
Relative Humidity
The relative humidity indoors ranged from 23.2 percent to 58.3 percent. One hundred and fifteen • (115) measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. Thirteen (13) indoor measurements were within the ASHRAE recommended range. The outdoor relative humidity range was 21.4 to 26.4 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations iiidoors ranged from 491 ppm to 1082 ppm. All of the measurements were below the ASHRAE Standard 62-1999 recommended maximum . concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 643 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1343 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors was 2 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were 2-4 ppm.
Respirable Particulates (PM2_§)
Respirable particulate concentrations* indoors ranged between 11 pg/m^ to 48 pg/m^ with an average 26 pg/m^- None of the indoor measurements were above the NPAAQS of 65 pg/m^ 24- hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Two (2) of the one-hundred twenty-eight (128) instantaneous measurements were above the USEPA recommended concentration for sensitive individuals such as asthmatic people and children of 40 pg/m^. The outdoor respirable particulate concentrations ranged from 64 pg/m3 to 123 pg/m3 with an average of 93 pg/m^. Eleven (11) of the outdoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. All of the outdoor instantaneous measurements
CITY_21MC100_002865692
NYC-WTC_000370442
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000370524
Indoor air quality measurements collected March 20, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370473
March 11, 2002 IAQ measurements report for the BOE school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000211863
Letter and report from ATC Associates detailing indoor air quality measurements collected at the school on March 27, 2002, to evaluate possible contamination.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370529
Indoor air quality measurements collected March 21, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000296749
ATC memo reporting indoor air quality measurements at 90 Trinity Place for HS for Leadership & [name], Apr 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394729
Indoor air quality report for High School for Leadership & [name], Apr 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370557
ATC reports IAQ measurements taken March 26, 2002 at High School for Leadership & [name].
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370411
ATC IAQ measurements conducted March 5, 2002 at the referenced NYC BOE school.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000189397
Report of indoor air quality measurements collected at a school on April 9, 2002, to determine if acceptable air quality is maintained.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000274734
ATC IAQ measurements collected March 7, 2002 at PS 89M for NYC BOE.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394850
ATC IAQ report for High School for Leadership & [name], Trinity Place, April 2002.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000383791
Indoor air quality measurements collected March 7, 2002 at PS89M for BOE evaluation.
12 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000394734
Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000189397
Report of indoor air quality measurements collected at a school on April 9, 2002, to determine if acceptable air quality is maintained.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370524
Indoor air quality measurements collected March 20, 2002 at the referenced school.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000296754
ATC memo with IAQ measurements at HS for Leadership & [name], Apr 11, 2002, BOE request.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394768
Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370422
Indoor air quality measurements collected March 6, 2002 at the referenced school.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
Indoor air quality measurements collected March 20, 2002 at the referenced school.
Similar indexed content
March 11, 2002 IAQ measurements report for the BOE school.
Similar indexed content
Letter and report from ATC Associates detailing indoor air quality measurements collected at the school on March 27, 2002, to evaluate possible contamination.
Similar indexed content
Indoor air quality measurements collected March 21, 2002 at the referenced school.
Similar indexed content
ATC memo reporting indoor air quality measurements at 90 Trinity Place for HS for Leadership & [name], Apr 2002.
Similar indexed content