Mr. Bernard P. Orlan June 17, 2002
Indoor Air Quality Assessment Page 3
P. S. 89M ATC Project No. 15-19125-0297
Real-Time Environmental Measurements
ATC collected seventy-nine (80) sets of real-time environmental measurements consisting of
seventy (70) from inside the school building and ten (10) from outdoors. All five floors of the
school building were surveyed. These results are described below.
Field data sheets are found in Attachment 1, Readings began at 8:00 A.M, and concluded at
approximately 11 rOO A.M.
Temperature
Indoor dry bulb temperature measurements ranged from 69.1 °F to 72.6 °F. All of the indoor
measurements for temperature were below the range of 73 to 79°F (at 50 percent relative
humidity) as recommended by the ASHRAE Standard 55-1992 during the summer season. The
outdoor temperature measurements ranged from 60.3 °F to 60.4 °F.
Relative Humidity
The relative humidity indoors ranged from 47.3 to 56.9 percent. All of the indoor measurements
for relative humidity were within the ASHRykE-recommended range of 30 to 60 percent for
occupant comfort. The outdoor relative humidity measurements were 65.4 percent for all
readings.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 561 ppm to 1461 ppm. One (1) of the indoor
measurements for CO2 was above the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The maximum outdoor (background)
CO2 concentration was 553 ppm. Therefore, the maximum acceptable level of CO2 at this
location was 1253 ppm (background level -1- 700 ppm). The highest measurement was recorded in
room 219 at 11:00AM with 30 occupants. Carbon dioxide measurements are used as an indicator
of available outside makeup air. The primary source of CO2 indoors is occupant respiration. The
school building was occupied during ATC’s assessment.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 1 ppm for all readings. These concentrations were
below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration were 1 ppm
for all collected readings.
Respirable Particulates (PM2d
Respirable particulate concentrations* indoors ranged between 8 pg/m’to 21 pg/m\ The average
PM2.5 concentration for the entire school building was approximately 15 pg/m\ None of the
indoor measurements were above the NPAAQS of 65 pg/m’ 24-hour average concentration of
particulate matter 2.5 micrometers or less in aerodynamic diameter or above the USEPA
recommended concentration of 40 pg/m’ for sensitive individuals and children. The outdoor
respirable particulate concentration measurements ranged between 26 pg/m’ to 30 g/m’ with an
average of 28 pg/nT.