Indoor air quality report, PS 89M, May 2002

Machine-extracted title · confidence 58%

ATC IAQ measurements collected at PS 89M; May 2002.

NYC-WTC_000369769–000369772
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan May 13, 2002 Indoor Air Quality Assessment Page 3 P. S. 89M ATC Project No. 15-19125-0297

Real-Time Environmental Measurements

ATC collected eighty (80) sets of real-time environmental measurements consisting of seventy- one (71) from inside the school building and nine (9) from outdoors. All five floors of the school building were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded at approximately 11:30 A.M.

Temperature

Indoor dry bulb temperature measurements ranged from 70 °F to 76 °F. Fifteen (15) of the indoor measurements for temperature were below the range of 73 to 79°F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the summer season . The outdoor temperature measurements ranged from 68.3°F to 69.9 °F.

Relative Humidity

The relative humidity indoors ranged from 44.8 to 54.3 percent. All indoor measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 53 to 55.5 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 702 ppm to 1874 ppm. Five (5) of the indoor measurements for CO2 were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 661 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1361 ppm (background level + 700 ppm). The highest reading was measured in room 404 at 10:00 AM with 29 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO, indoors is occupant respiration. The school building was occupied during ATC’s assessment.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors ranged from 1 ppm to 2 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 1 ppm for all collected readings.

Respirable Particulates (PM2 s)

Respirable particulate concentrations* indoors ranged between 20 pg/m' to 50 pg/m\ The average PM25 concentration for the entire school building was approximately 33 pg/m\ All of the indoor measurements were below the NPAAQS of 65 pg/m’ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Ten (10) of the seventy-one (71) instantaneous indoor readings were above the USEPA recommended concentration of 40 pg/m’ for sensitive individuals and children. The outdoor respirable particulate concentration measurements ranged from 90 to 100 pg/m'with an average of 95 pg/m’.

CITY_21MC100_002864337

NYC-WTC_000369771

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000369771Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000199027

Cover letter from ATC Associates submitting indoor air quality measurement results for PS89M collected on May 22, 2002.

Similar indexed content

IAQ report, P.S. 89M, May 2002

NYC-WTC_000369857

Indoor air quality report for PS/89M school, measurements collected May 22, 2002.

Similar indexed content

Compare copies and versions →