Mr. Bernard P. Orlan May 16, 2002 Indoor Air Quality Assessment Page 3 P. S. 89M ATC Project No. 15-19125-0297
Real-Time Environmental Measurements
ATC collected eighty (80) sets of real-time environmental measurements consisting of seventy- one (71) from inside the school building and nine (9) from outdoors. All five floors of the school building were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded at approximately 11:30 A.M.
Temperature
Indoor dry bulb temperature measurements ranged from 61.4°F to 75.6 °F. Sixty-nine (69) of the indoor measurements for temperature were below and two (2) were within the range of 73 to 79°F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the summer season . The outdoor temperature measurements ranged from 55°F to 56.1 °F.
Relative Humidity
The relative humidity indoors ranged from 27 to 37.2 percent. Thirty-three (33) of the indoor measurements for relative humidity were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 28,3 to 29.8 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 437 ppm to 1053 ppm. All of the indoor measurement for CO2 were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 436 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1136 ppm (background level + 700 ppm). Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant respiration. The school building was occupied during ATC’s assessment.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 1 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were 1 ppm for all collected readings.
Respirable Particulates (PM2 §)
Respirable particulate concentrations* indoors ranged between 5 pg/m^ to 18 pg/m^. The average PM2.5 concentration for the entire school building was approximately 11 pg/m-. All of the indoor measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentration measurements ranged from 17 to 25 pg/m^ with an average of 22 pg/m^.
CITY_21MC100_002886880
NYC-WTC_000392866
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000313667
ATC measurements for PS 89M on May 15, 2002, temperature and humidity.
14 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000313589
Indoor air quality measurements collected at PS 89M for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394489
Indoor air quality report for PS 89M with April 26, 2002 measurements.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000369801
ATC IAQ measurements at PS 89M for BOE; May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394477
IAQ measurements collected April 25, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394514
IAQ measurements collected April 30, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394392
April 2002 indoor air quality measurements at PS 89M (series).
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000369857
Indoor air quality report for PS/89M school, measurements collected May 22, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000369711
ATC IAQ measurement report for PS 89M school, May 2002, for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000199027
Cover letter from ATC Associates submitting indoor air quality measurement results for PS89M collected on May 22, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000313544
Indoor air quality measurements collected at PS 89M for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000369881
ASME/BOE IAQ measurements report for P.S. 89M, May 24, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000313667
ATC measurements for PS 89M on May 15, 2002, temperature and humidity.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370073
ATC IAQ measurement report for PS 89M at date of June 18, 2002.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000369789
ATC IAQ measurements at PS 89M for BOE; May 2002.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000313893
ATC IAQ measurements collected June 18, 2002 at PS 89M per BOE request.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000313964
ATC report of IAQ measurements at P.S. 89M, June 25, 2002, for school air quality evaluation.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000328340
ATC provides IAQ measurements for PS 89M; BOE requested air quality evaluation.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000313667
ATC measurements for PS 89M on May 15, 2002, temperature and humidity.
Similar indexed content
NYC-WTC_000313589
Indoor air quality measurements collected at PS 89M for BOE.
Similar indexed content
NYC-WTC_000394489
Indoor air quality report for PS 89M with April 26, 2002 measurements.
Similar indexed content
NYC-WTC_000369801
ATC IAQ measurements at PS 89M for BOE; May 2002.
Similar indexed content
NYC-WTC_000394477
IAQ measurements collected April 25, 2002 at the referenced school.
Similar indexed content