GOLDEN — CORPORATION Occupational Health, Safety & , Environmental Consultants

September 25, 2001

Mr. William Link University Director of Facilities Pace University 235 Elm Rd. Dow Hall Briarcliff Manor, NY 10510

Re: Air Quality Sampling Report Pace Plaza Golden Project No. 01204

Dear Bill:

In response to your request, Golden conducted additional asbestos air monitoring at One Pace Plaza on September 18, 2001.This data supplements the data presented in our report dated September 18, 2001.

The air sampling was conducted in representative areas through out the Pace Plaza campus. All air samples were conducted while the air handlers were operating. Air samples were analyzed by Scientific Laboratory in NY, NY using Transmission Electron Microscopy in accordance with the EPA AHERA method.

All air sample results were within safe limits established by the Environmental Protection Agency (EPA) the New York State Department of Labor (NYS DOL) and the New York City Department of Environmental Protection (NYC DEP). A summary of the air sample data is presented below in Table 1.0.

Table 1.0 09-18-01 Asbestos Air Sample Results - 1 Pace Plaza Sample Location Sample ID Time of Sample Analysis Result 17“ Fl. - East Towers, North Lounge 01204-40 10:02-12:48 No Asbestos Structures Detected 15“’ Fl. - East Tower, South Lounge 01204-41 10:02-12:48 No Asbestos Structures Detected 1T'’ Fl. - East Tower, Elevator Lobby 01204-42 10:10 - 12:54 No Asbestos Structures Detected 10'*’ Fl. - East Tower, North Lounge 01204-43 10:14-12:56 No Asbestos Structures Detected 8'*' Fl. - East Tower South Lounge 01204-44 10:18-13:00 No Asbestos Structures Detected 6'^ Fl. - East Tower, North Lounge 01204-45 10:22-13:02 No Asbestos Structures Detected 4'" Fl. - East Tower, Hall by Elevators 01204-46 10:26-13:06 No Asbestos Structures Detected 2”“ Fl. - East Tower, Library / AC#5 01204-47 10:32-13:08 No Asbestos Structures Detected Outdoors - r* Floor, North Side 01204-49 13:15-16:26 No Asbestos Structures Detected 6* Fl. West Tower, East Hall / HVAC-3 01204-50 13:20 - 15:52 No Asbestos Structures Detected 4'" Fl. West Tower, Business Office / 01204-51 13:24-15:55 No Asbestos Structures Detected HVAC 1,2,4,5____________________ 4'" Fl. West Tower, Classroom 401 / 01204-52 13:28-15:58 No Asbestos Structures Detected HVAC 1,2,4,5

Robert Morris Building • 100 North 1 T'h Street, 9“’Floor • Philadelphia, PA 19103 Tel 215 496 9237 • Fax 215 496 9280 • Toll Free 800 586 5580 • www.colden.com

CITY_21MC100_002849914

NYC-WTC_000366583

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000366583Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000366571

Pace University air sampling report addressing asbestos concerns and testing in Pace Plaza.

Similar indexed content

NYC-WTC_000366591

Chain-of-custody and sampling report for Pace Plaza asbestos air monitoring.

Similar indexed content

NYC-WTC_000321175

Asbestos sampling results; most below standard; one not submitted; PCB/Metals results noted.

Similar indexed content

Compare copies and versions →