NYC 9/11 Public Portal Document
104 East 25th
New York, M-a York
wwrw.atc-envii
ASaCCIXTES
SiM INC.
2,2.35 ■
Pax 212351
VIA FACSIMILE: 212-206-5680 (1 pa go)
October 8. 2001
Mr. Brian Becker
Tim© Equities Management
55 Fifth Avenue, 1 S'" Floor
New York. NY
RE; Asbestos Ambient Air Sampling Results
47 West Street and 80 Washington Street
Dear Mr. Becker
ATC Associates Inc. (ATC) is pleased to submit this summary report presenting the asbestos
ambient air sample results for 47 West Street and 80 Washington Street.
On September 26, 2001 ATC collected a total of thirty arnbient air samples from within 47 West
Street followed by the collection of 11 eleven ambient air samples from within 80 Washington
Street on September 29, 2001 to ascertain the presence or absence of airborne asbestos All
samples collected were analyzed In accordance with the AHERA Transmission Electron
Microscopy (TEM) method as set forth at 40 CFR Part 763, Subpart 6, Appendix A. Acceptable
ambient air samples results are those sample sets meeting the AHERA re-occupancy
requirement following an asbestos abatement action of an average of less than 70 asbestos
structures per square millimeter (<70 s/mm’).
Summary of Ambient Air Sample Results
Building Analytical Result
47 West S^et ^AuTampies^TOj^m^
uO Washington Street Al samples <70 s/mrri^
Based upon the analytical results of less than 70 asbestos structures per square mllllrneter (<7D
s/mm’) which is within'the AMERA clearance requirement, It is ATC's opinion that the ambient
air samples collected throughout th© two buildings meet an acceptable criterion for re
occupancy. If you have any questions or require additional explaination of the information
presented please do not hesitate to call me at 212-353-8280
Sincerely,
Fred Burkhardt — Siitt Oral
Senior Project Manager Sei..,^,
ATC Associated Inc. ATC Associates Inc.
CITY_21MC100_002859893
NYC-WTC_000363716
OCR can misread numbers and units. Confirm readings against the page image before using them.