03/13/2002 12:29 FAX 212 353 8306 ATC ®005

Mr. Bernard P. Orlan March 13,2002 Indoor Air Quality Assessment Page 4 P- S- S9M ATC Project No- 15-19125-0297 from 39 to 52 gg/m^ with an average of 43 gg/m^. Seven (7) of the outdoor measurements were above the EPA recommended guideline for children and sensitive individuals of 40 gg/m^ ■

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

JVOC Concentrations

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following; • The school building was occupied at the time of the assessment. • No smoke odor was detected in tire building • The interior of the building appeared clean and free of dust and debris.

FINDINGS

Based on the real-time raeasnremcnts, tire following findings are presented:

1. Concentrations of CO and TVOCs were within applicable standards and guidelines. 2. All of the indoor measurements of relative humidity were below tlie ASHRAE recommenced range of 30 to 60 percent for occupant comfort. 3. Three (3) of die temperature measurements were below the range of 68 to 75°F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the heating season (wintertime conditions). 4. All CO2 measurements were within the range recommended by ASHRAE 62-1999, 5. Seven (7) of the outdoor respirable particulates measurements were above the EPA recommended guideline for children and sensitive individuals of 40 gg/m^.

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about tliis report, please call (212) 353-8280, extension 211 or 212.

Sincerely, Reviewed by; ATCASSOClAr£S INC.

Yiannis Efstathiou James R. Cohn, CIH, CSP Project Manager Regional Manager Industrial Hygiene Division Attachment

CITY_21MC100_009253508

NYC-WTC_000360212

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000360212Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →