03/07/2002 09:41 FAX 212 353_830e ATC 1^005/014

Mr. Bernard P. Orlan March 7,2002 Indoor Air Quality Assessment Page 4 P. S. 89M________________ ATC Project No. 15-19125-0297

individuals and children. The outdoor respirable particulate concentration measurements ranged from 20 to 29 pg/m^ with an average of 24 pg/m^.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

Type Concentt'giions

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted tire following; • Tire school building was occupied at the time of the assessment • No smoke odor was detected in the building • The interior of the building appeared clean and free of dust and debris.

FINDINGS

Based On the real-time measurements, the following findings arc presented:

1. Concentrations of Respirable particulates, CO, CO2 and TVOCs were within applicable standards and guidelines 2. All of the indoor measurements of relative humidity were below the ASI-IRAE recommended range of 30 to 60 percent for occupant comfort. 3. All the temperature measurements were within the range of 68 to 7S®F (at 50 percent relative humidity) as recommended by tlic ASHRAE Standard 55-1992 during the heating season (wintertime conditions).

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, ext # 356

Sincerely, J TCASSOCLiTJSS /NC. Reviewed by:

Prasad Doddapancni James R. Cohn, CIH, CSP Project Manager Regional Manager Industrial Hygiene Division Attachment:

CITY_21MC100_012158165 NYC-WTC_000360233

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000360233Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →