NYC 9/11 Public Portal Document
JLC ENVIRONMENTAL CONSULTANTS, INC.
200 Park Avenue South, Suite 1001, New York, New York 10003
Phone; (212) 420-8119 Fax: (212) 420-6092
Project No.: 01-2102
Metcalf & Eddy Inc. ELAP Lab Code; 11029
Analyte; ASBESTOS
3 Werner Way, Suite 310 NIOSHand AiHAlsbCode; 100273
Date Received: 9/29/01
Lebanon, NJ 08833 NVLAP Lab Code: 101953
Date Analyzed: 9/29/01
Batch #: 0109B386
SUMMARY OF ANALYTICAL RESULTS - PLM
Site: 3 World Financial Center - Floors 3-26
SAMPLE #
ASBESTOS TOTAL % OF CONSTITUENTS
DATE DESCRIPTION /LOCA TION COLOR DETECTED? ASBESTOS CONSTITUENTS
COLLECTED
LAB#
CLIENT'S SAMPLE #
20005 20th Floor/ Area of Damage/ South East WHITE NO 0% CELL 5%
9/27/01 Corner of Building/ Sample of Debris NFIB 95%
11111
20-005
20006 20th Floor/ Area of Damage/ South East GRAY/ NO 0% CELL 5%
BLACK FBGL 5%
9/27/01 Comer of Building/ Sample of Debris
11112 NFIB 90%
20-006
20007 20th Floor/ Area of Damage/ South East WHITE YES 30.8% CHRY 30.8%
NFIB 69.2%
9/27/01 Corner of Building/ Sample of Debris
11113
20-007
20008 20th Floor/ Area of Damage/ South East BROWN NO 0% CELL ■ 20%
9/27/01 Corner of Building/ Sample of Debris NFIB 80%
11114
20-008
'INSUFFICIENT MATERIAL SUBMITTED **TEM RECOMMENDED —NOT ANALYZED POSITIVE STOP
ASBESTOS CONSTITUENTS NON-ASBESTOS CONSTITUENTS
Sample Analysis by:
Polarized Light Microscopy-Dispersion Staining (PLM-DS) CHRY = Chrysotile Asbestos PAPF = Paper Fiber
AMOS = Amosite Asbestos MINW = Mineral Wool
CROC = Crocidolite Asbestos FBGL = Fiberglass
Method of Sample Preparation and Analysis: ACTN = Actinolite Asbestos SYNF = Synthetic Fibers
All samples were prepared and analyzed in accordance with the EPA TREM = Tremolite Asbestos CELL = Cellulose
"Method for the Determination of Asbestos in Bulk Building Materials" ANTH = Anthophylite Asbestos NFiB= Non-Fibrous
USEPA/ 600/ R-93/116, July 1993. ORGM = Organic Material
WOLL = Wollastonite
Inslrumentation' HSHR = HoiseHair
OTHR = Other
Olympus PLM, Model BH-2/VM Stereomicroscope, Model
VMZ 1x-4x. Gulam Machhiwala
Laboratory Director
Analytical results reflect the make up of the materials only in the areas sampled. This "Summary of Analytical Results" shall not be reproduced except in full, without the writte
approval of JLC Laboratory, and it must not be used by client to claim product endorsement by NVLAP or any agency of (he U.S. Governmen! This method is not applicable to •
samples containing large amounts of fine fibers below the resolution of the light microscope. The value of Ihis method is limited to the quonliiatue identification of asbestos
and the semi-quantHative rietermi nation of asbestos content of bulk samples, expressed as a percentage of the protected area. Quantitation of asbestos content was
determined with a visual volume estimate, a calibrated visual area estimate, and/or pont counting procedure. CAUTION: Other fibers vith optical properties similar Io asber/ o
may give positive interferences and will be considered asbestos under this methodology. Also, PLM is not consistently reliable in delecting asbestos in floor coverings and
similar non-friable organically-bound materials. Quantitative transmission electron microscopy is currently the only method that can be used to determine if this material can bz
considered or treated as non-asbestos containing.
Page 2 of 3
CITY_21MC100_011914204
NYC-WTC_000357504
OCR can misread numbers and units. Confirm readings against the page image before using them.