NYC 9/11 Public Portal Document
INDEPENDENT TESTING LABODATOEHES, INC.
a
,11J
“SERVING INDUSTRY WORLDWIDE SINCE 1973”
129-11 ISfk Avenue - College Point, N,Y, 11356
J (718) 96D8630 Fax (718) 769=1337
Page 2 of3 Client: I-ntesa BCI
October 22,2001
DR] r; WATER ANALYSTS
Project..I..ocatiniT 1 William Street f 5'*'FL Men’s Bathroom)
Lab ID Location Parameter (s) Limit Results
A2407 fl) 5*" El I’s Bathroom Total Coliform Bact. Negative Negative
A2407 (1) 5*“* Fl Men’s Bathroom E. Coli Absent Absent
A2407 fl) 5*** Fl Men’s Bathroom _____ Chloride_____ 250 mg/L 10 mg/L
A2407 (1) 5* Fl Men’s Bathroom Nitrate 0.33 mg/L <0.1 mg/L
A2407 (1) 5*'* Fl Men’s Bathroom Nitrite 10.0 mg/L <0.10 mg/L
A2407 fl) 5* Fl Men’s Bathroom ________ BH________ NA 6.95 units
A2407 fl) 5*** Fl Men’s Bathroom Specific Conductivity NA 88 umhos
A2407 fl) 5*** Fl Men’s Bathroom CoDuer, Cu 1.0 mg/L 0.09 mg/L
A2407 fl) 5*** Fl Men’s Bathroom ______ Iron, Fe______ 0.30 mg/L <0.05 mg/L
A2407 fl) 5* Fl Men’s Bathroom Manganese, Mn 0.30 mg/L <0.05 mg/L
A2407 (1) 5*** Fl Men’s Bathroom Lead, Ph 15.0 ug/L 1.4 ug/L
A2407 fl) 5*** Fl Men’s Bathroom Zinc, Zn 5.0 mg/L <0.05 mg/L
Results reported exceed New York State USEPA limits for potable water.
Results reported meet [USEPA Action Level] for potable water.
DR r: WATER ANAT.YSTS
Project Tvocation: 1 William Street (Basement)
Lab IP Location Parameter (s) Limit Results
A2407 f2) Basement Total Coliform Bact. Negative Negative
A2407 f2) Basement E.Coli Absent Absent
A2407 f2) Basement Chloride 250 mg/L 12 mg/L
A2407 (2) Basement ______ Nitrate______ 0.33 mg/L <0.1 mg/L
A2407 (2) Basement ______ Nitrite______ 10.0 mg/L <0.10 mg/L
A2407 (2) Basement ______ eH_____ NA 6.95 units
A2407 f2) Basement Specific Conductivity NA 87 umhos
A2407 f2) Basement Copper, Cu 1.0 mg/L 0.07 mg/L
A2407 (2) Basement ______ Iron, Fe______ 0.30 mg/L <0.05 mg/L
A2407 (2) Basement Manganese, Mn 0.30 mg/L <0.05 mg/L
A2407 (2) Basement _____ Lead, Ph_____ 15.0 ug/L 42.3 ug/L
A2407 f2) Basement Zinc, Zn 5.0 mg/L <0.05 mg/L
Results reported exceed New York State USEPA limits for potable water.
Results reported meet [USEPA Action Level] for potable water.
CITY_21MC100_003008819
NYC-WTC_000343100
OCR can misread numbers and units. Confirm readings against the page image before using them.