NYC 9/11 Public Portal Document
Ambient Group, Inc. Water Analysis Report
ELAP# 10866
Client: CHASE Date Sampled: 9(16/01
Building Address: 15 BROAD STREET Date Submitted: 9/17/01
Sample Location: 2ND FLOOR: MEN'S ROOM Date Reported: 9/18/01
HANDICAPPED SINK
Sampled By: JACK SPRINGSTON
Prolect ID: 211352-02 Eh Tn! ARa74
Parameter Over Sample Units Safe Drinking Standard
Limit(*) Water Act Standards Type -
Cadmium <0.006 mg L 0.01 MCL
Calcium 6.62 mg/L
Chromium <0.003 mg/L 0.05 MCL
Copper 0.204 _mg/L 1.3 1.0 AL / RCL
Iron <0.203 m /L 0.3 RCL
Lead <0.001 mgfL 0.015 • AL
Magnesium 1.65 mg/L
Manganese 0.007 m /L 0.05 RCL
Nickel <0.005 mg/L
Sodium 8.54 mg/L
Zinc 0.503 m L 5 RCL
Fluoride 0.87 mgfL 4 : MCL
Chloride 13.14 mglL 250 RCL
Nitrite <0,01 mg,L L MCL
Nitrate 0.28 mg/L 20 MCL
Phosphate 0.35 mg/L
Sulfate 5.88 mg/L 250 RCL
H - Field 7.04 Units 6.5-8.5 RCL
pdfiC Conductance 102.90 uS/cm
Coliform Bacteria Absence P A Absence MCL
E. Coll Bacteria Absence P/A Absence MCL
Codes: MCL ( Maximum Contaminant Level), RCL ( Recommended Contaminant Level),
AL ( EPA Action Level), mg/L ( milligrams/liter ppm ), * Indicates analyte exceeds
a
EPA/SDWA proposed maximum contamination level, uS/cm ( microsiemens ),
P / A ( Presence / Absence)
Signature:
Michael Borelio, M.S,
Laboratory Manager
091-d 910/910d 096-1 pee, 96Z ZlZ I 1N303DVNVW 9NIG11119-WOJd Wdeq:l0 Z00Z-9Z-q®d
NYC-WTC 000105351
OCR can misread numbers and units. Confirm readings against the page image before using them.