NYC 9/11 Public Portal Document
Ambient Group, Inc. Water Analysis Report
ELAP#10865
client: CHASE Date Sampled: 9/16/01
Building Address: 15 BROAD STREET Date Submitted: 9/17/01
Sample Location: 24TH FLOOR: MEN'S ROOM SINK Date Reported: 9/18/01
Sampled BY: JACK SPRINGSTON
Protect ID: 211352-01 Leb IDe 38373
Parameter Over Sample Units Safe Drinking Standard
Limit(*) Water Act Sendards Type
Cadmium <0.006 mg/L 0.01 MCL
Calcium 6.64 mg/L
Chromium <0.003 mg/L 0.05 MCL
Copper 0.222 mg/L 1.3 / 1.0 AL I RCL
Iron <0.203 mg/L 0.3 RCL
Lead <0.001 mg/L 0.015 AL
Magnesium 1.60 mgfL
Manganese 0.008 mg jL 0.05 RCL
Nickel <0.005 mg/L
Sodium 8.27 mg/L
Zinc 0.364 mg/L 5 RCL
Fluoride 0.93 mg/L 4 MCL
Chloride 13.02 mg/L 250 RCL
Nitrite <0.01 mglL i MCL
Nitrate 0.33 /L 10 MCL
Phosphate 0.37 /L
Sulfate 6.1 mg/L 250 RCL
pH - Field 7.01 Units 6.5-8.5 RCL
Specific Conductance 97.50 uS/cnq
Coliform Bacteria Absence P/ A Absence MCL
E. Coll Bacteria Absence P/ A Absence MCL
Codes: MCL ( Maximum Contaminant Level ), RCL ( Recommended Contaminant Level),
AL ( EPA Action Level), mg/L ( milligrams/liter - ppm ), * indicates analyte exceeds
EPA/SDWA proposed maximum contamination level, uS/cm ( microsiemens ),
P / A ( Presence / Absence)
Signature:
Michael Borello, M.S.
Laboratory Manager