05/24/2002 OS.•32 FAX 212 353 8308 __ ATC @004

Mr. Bernard P, Orlan May 23, 2002 ; I Indoor Air Quality Assessment Page 3 P. S. 89M ___________________________ ATC Project No. 15-19125-0297 Real-Time E?4VJronmental Measurjements

ATC collected seventy-nine (80) sets of real-time environmental measurements consisting of seventy-one (71) from inside the school building and nine (9) from outdoors. All five floors of the school building were surveyed. These results are described below.

Field data sheets are found in Attachment 1- Readings began at S:00 A,M. and concluded at approximately 11:30 A.M. I J Temperature I i Indoor dry bulb temperature measurements ranged from 67.5"F to 74 ®F. Fifty-eight (58) of the indoor measurements for temperature were below the range of 73 to 79'’F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the summer season , The outdoor temperature measurements ranged from 59.6 ’F to 60.3 "F.

Relative Hu/tiidity

The relative humidity indoors ranged from 26.3 to 32.3 percent. Sixty-two (62) of the indoor measurements for relative humidity were below tlie ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 33.1 to 34.0 percent.

Carhon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 544 ppm to 1199 ppm. All of the indoor measurements for CO2 were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm. above the background level. The maximum outdoor (background) CO2 concentration was 568 ppm. Therefore, the maximum acceptable level of CO2 at tins location was 1268 ppm (background level + 700 ppm). Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO? indoors is occupant respiration. The school building was occupied during ATC’s assessment.

Carhon Monoxide Concentration

Carbon monoxide concentrations indoors ranged from 1 ppm to 2 ppm. Tliese concenUations i1 were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were 2 ppm for all collected readings.

Resvirable Particulateti (PM2.5)

Respirable particulate concentrations* indoors ranged between 6 pg/m^ to 20 pg/m^. The average PM2.5 concentration for die entire school building was approximately 11 ug/m^. All of the indoor measurements were below the NPAAQS of 65 pg/ni^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and tlic USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentration measurements ranged from 23 to 26 pg/m3 with an average of24pg/m3.

i

CITY_21MC100_009261557

NYC-WTC_000340591

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000340591Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →