IAQ report, P.S. 89M, May 2002

Machine-extracted title · confidence 42%

ATC IAQ measurements conducted May 2, 2002 for P.S. 89M, NYC DOE.

NYC-WTC_000340699–000340702
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

05/03/2002 12:56 FAX 212 353 8306 @004

Mr. Bernard P, Orlan May 3,2002 Indoor Air Quality Assessment Page 3 P. S, 89M__________________________ ATC Project No. 15-1912S-Q297 real-Time environmental measurements

ATC collected eighty (SO) sets of real-time environmental measurements consisting of seventy (70) from inside the school building and ten (10) from outdoors. All five floors of the school building were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 8:00 A.M, and concluded at approximately 11:30 A.M.

Temperature

Indoor dry bulb temperature measurements ranged from 65.0 ’F to 73.8 ’F. Seventy-six (76) of the indoor measurements for temperature were below the range of 73 to 79“F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the summer season, The outdoor temperature measurements ranged from 50.6‘F to 52.7®F.

Relative Humidity

The relative humidity indoors ranged from 36.4 to 59.4 percent. All of the indoor measurements for relative humidity were within the ASURAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 54.0 to 57,3 percent.

Carban Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 535 ppm to 1120 ppm. All of the indoor measurements for CO2 were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 468 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1168 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant respiration. The school building was occupied dining ATC’s assessment.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 1 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm- The outdoor CO concentration were also 1 ppm for all collected readings.

Respirable Particulates (PMyj)

Respirable particulate concentrations* indoors ranged between 10 pg/m^ to 38 tlg/m^. The average PM2.5 concentration for the entire school building was approximately 18 g/m3. All of the indoor measurements were below the NPAAQS of 65 p.g/m3 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and die USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentration measurements ranged from 34 to 42 jxg/m^ with an average of36j.igZm3.

CITY_21MC1OO_OO9261676 NYC-WTC_000340701

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000340701Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000199015

Cover letter from ATC Associates submitting indoor air quality measurement results for PS89M collected on May 16, 2002.

Similar indexed content

Compare copies and versions →