NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 4 pages

Indoor air quality report, Stuyvesant High School, May 2002

Machine-extracted title · confidence 42%

May 2002 IAQ measurements at Stuyvesant High School, BOE request.

NYC-WTC_000336093–000336096
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan May 13,2002 Indoor Air Quality Measurements Page 4 Stuvvesant High School (M477) ATC Proiect No. 15-19125-0246

In addition to higher efficiency rating filters on their HVAC units, portable High Efficiency Particulate Air (HEPA) purifiers were placed in Rooms 327, 333, 638 and 740. The I’M2.5 concentration range for these rooms was 22 - 35 pg/m^ with an average of approximately 29 pg/m3.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

T7OC Concentration TVOCs inside the building were 0.0 ppm for all readings. The outdoor TVOC concentrations were also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building;

FINDINGS

Based on the real-time measurements, the following findings are presented; 1. Concentrations of CO , and TVOCs were below applicable standards and guidelines. 2. Forty-nine (49) measurements of relative humidity were above the ASHRAE recommended range of 30 to 60 percent for occupant comfort. 3. One hundred and two (102) temperature measurements were below the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the mechanical cooling season (summertime conditions). 4. Both outdoor respirable particulate measurements were above the USEPA recommendation of 40 ug/m-’ for sensitive individuals and children. 5. Three (3) CO2 measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level.

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, extension 211 or212. Sincerely, A TC ASSOCIA TES INC.

Reviewed hvr

' Yiannis Efstathiou James R. Colm, CIH, CSP Senior Project Manager Regional Manager, Industrial Hygiene Division

Attachment

CITY_21MC1OO_OO3O6O724 NYC-WTC_000336096

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000336096Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →