IAQ memo, Stuyvesant HS, Apr 2002

Machine-extracted title · confidence 42%

April 19, 2002 IAQ memo for Stuyvesant High School.

NYC-WTC_000406596–000406599
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan April 19, 2002 Indoor Air Quality Measurements Page 4 Stuvvesant High School ('M477) ATC Project No. 15-19125-0246

In addition to higher efficiency rating filters on their HVAC units, portable High Efficiency Particulate Air (HEPA) purifiers were placed in Rooms 327, 333, 638 and 740. The PM2.5 for these rooms concentration ranged from 14 -24 pg/m^ with an average of approximately 18.5 pgrnY

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

TVOC Concentration TVOCs inside the building wereO.O ppm for all readings. The outdoor TVOC concentrations were also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following; • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building;

FINDINGS

Based on the real-time measurements, the following findings are presented: 1. Concentrations of CO2, CO , and TVOCs, were below applicable standards and guidelines. 2. All of the measurements were within the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during summer conditions. 3. One (1) measurement was above and one hundred-seventeen (117) measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. 4. All of the indoor measurements for PM2.5 were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommendation of 40 pg/m^ for sensitive individuals and children.

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, extension 211 or 212.

Sincerely, .1TC ASSOCIA TES INC.

Reviewed by: ''

'■^jnel Java^ James R. Cohn, CIH, CSP Senior Project Manager Regional Manager, Industrial Hygiene Division

Attachment

CITY_21MC1OO_OO29O2773

NYC-WTC_000406599

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000406599Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000336237

IAQ measurements collected April 19, 2002 at Stuyvesant High School.

Similar indexed content

Compare copies and versions →