Mr. Bernard P. Orlan March 13, 2002 Indoor Air Quality Measurements Page 4 Stuvvesant High School ('M477) ATC Project No. 15-19125-0246

In addition to higher efficiency rating filters on their HVAC units, portable High Efficiency Particulate Air (HEPA) purifiers were placed in Rooms 327, 333, 638 and 740. The PM2.5 concentration range for these rooms was 7-21 pg/m^ with an average of approximately 14 pg/m3.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

TVOC Concentration

TVOCs inside the building wereO.O ppm to 0.1 ppm The outdoor TVOC concentrations were 0.1 ppm to 0.2 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building;

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Measurements of temperature and concentrations of respirable particulates, CO ,CO2, and TVOCs, were within applicable standards and guidelines. 2. Sixty-five (65) measurements of relative humidity were below the ASHRAE recommended range of 30 to 60 percent for occupant comfort.

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, extension 211 or 212.

Sincerely, A TC ASSOCIA TES INC. Reviewed by:

Yiannis Efstathiou James R. Cohn, CIH, CSP Project Manager Regional Manager Industrial Hygiene Division

Attachment

CITY_21MC100_003061423

NYC-WTC_000336432

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000336432Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000402116

March 1, 2002 IAQ measurements report for Stuyvesant High School.

Similar indexed content

NYC-WTC_000269995

March 8, 2002 memo regarding IAQ sampling at Stuyvesant High School (M477).

Similar indexed content

Compare copies and versions →