NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan April 19, 2002 Indoor Air Quality Measurements Page 3 Stuyvesant High School (M477)_______________ ATC Project No. 15-19125-0246 Real-Time Environmental Measurements

ATC collected one hundred and twenty (120) sets of real-time environmental measurements consisting of one hundred and eighteen (118) in the school building and two (2) outdoors. All ten floors of the school were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded after 12:30 P.M.

Temperature

Indoor dry bulb temperature measurements ranged from 72.0 °F to 76.8 °F. All of the measurements were within the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during summer conditions. The outdoor temperature range was 75.6 to 76.2 °F.

Relative Humidity

The relative humidity indoors ranged from 50 percent to 61.2 percent. One (1) measurement was above and one hundred-seventeen (117) measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity levels were 56.2 and 59.7 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 415 ppm to 1171 ppm. All of the CO2 measurements were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations were 514 and 549 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1249 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors ranged from 0 ppm to 1 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 1 ppm to 2 ppm.

Respirable Particulates (PM2,5)

Respirable particulate concentrations* indoors ranged between 16 pg/m^ to 29 pg/m^ with an average of approximately 20 pg/mA All of the indoor measurements for PM2.5 were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommendation of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentrations were 29 and 31 pg/m3.

CITY_21MC100_002902772

NYC-WTC_000406598

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000406598Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000336237

IAQ measurements collected April 19, 2002 at Stuyvesant High School.

Similar indexed content

Compare copies and versions →