Mr. Bernard P. Orlan May 13,2002
Indoor Air Quality Measurements Page 3
Stuyvesant High School (M477)______________ ATC Project No. 15-19125-0246
Real-Time Environmental Measurements
ATC collected one hundred and twenty (120) sets of real-time environmental measurements
consisting of one hundred and eighteen (118) in the school building and two (2) outdoors. All
ten floors of the school were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded after
12:35 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 68.0°F to 73.6°F. One hundred and two
(102) of the measurements were below the range of 73 to 79°F (at 50 percent relative humidity)
recommended by ASHRAE Standard 55-1992 during the mechanical cooling season
(summertime conditions). The outdoor temperature range was 64.3 to 68.5°F.
Relative Humidity
The relative humidity indoors ranged from 52.6 percent to 63.7 percent. Forty-nine (49) of the
measurements were above the ASHRAE-recommended range of 30 to 60 percent for occupant
comfort.. The outdoor relative humidity levels were 57.2 and 59.2 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 509 ppm to 1175 ppm. Three (3) of the CO2
measurements were above the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The outdoor (background) CO2
concentrations were 426 ppm and 436 ppm. Therefore, the maximum acceptable level of CO2 at
this location was 1136 ppm (background level + 700 ppm). Levels above the recommended
maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator
of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged from 0 ppm to 1 ppm. These concentrations
were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were 1
ppm.
Respirable Particulates (PM2,5)
Respirable particulate concentrations* indoors ranged between 24 pg/m^ to 37 ug m3 with an
average of approximately 30 pg/m^. None of the indoor measurements were above the
NPAAQS of 65 pg/m3 24-hour average concentration of particulate matter 2.5 micrometers or
less in aerodynamic diameter or above the USEPA recommendation of 40 pg/m3 for sensitive
individuals and children. The outdoor respirable particulate concentrations were 41 and 67
pg/m^.