Mr, Bernard P. Orlan May 13, 2002 Indoor Air Quality Measurements Page 4 Stuwcsant High School (M477) ATC Project No. 15-19125-0246
In addition to higher efficiency rating filters on their HVAC units, portable High Efficiency Particulate Air (HEPA) purifiers were placed in Rooms 327, 333, 638 and 740. The PM2.5 concentration range for these rooms was 22 - 35 pg/m^ with an average of approximately 29 pg/m3.
♦ The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.
TTOC Concentradon TVOCs inside the building were 0.0 ppm for all readings. The outdoor TVOC concentrations were also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following; • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building;
FINDINGS
Based on the real-time measurements, the following findings are presented; 1. Concentrations of CO, and TVOCs were below applicable standards and guidelines. 2. Forty-nine (49) measurements of relative humidity were above the ASHRAE recommended range of 30 to 60 percent for occupant comfort. 3. One hundred and two (102) temperature measurements were below the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the mechanical cooling season (summertime conditions). 4. Both outdoor respirable particulate measurements were above the USEPA recommendation of 40 pg/m^ for sensitive individuals and children. 5. Three (3) CO2 measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level.
It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, extension 211or2l2. Sincerely, ATCASSOCIATES INC.
Revi^pH hy
'-Y'Yiannis Efstathiou James R. Cohn, CIH, CSP Senior Project Manager Regional Manager, Industrial Hygiene Division
Attachment
CITY_21MC100_002868497
NYC-WTC_000372910
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000406695
Indoor air quality measurements at Stuyvesant High School, May 2002, by ATC Associates for DOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000372830
Indoor air quality report for Stuyvesant High School dated May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000372941
ATC provides IAQ test results for Stuyvesant High School (M477) on May 15, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000270026
ATC IAQ measurements conducted March 15, 2002 at Stuyvesant High School for NYC BOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000229527
Report from ATC Associates detailing indoor air quality measurements collected at Stuyvesant High School on May 8, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336395
ATC IAQ measurements collected March 8–12, 2002 at Stuyvesant HS.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000204475
ATC Associates memo reporting indoor air quality measurements collected at a New York City Board of Education school in April 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000372847
Indoor air quality measurements collected May 6, 2002 at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406712
IAQ measurements collected on May 9, 2002 at Stuyvesant High School for DOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406544
April 12, 2002 memo detailing IAQ measurements at Stuyvesant High School.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406596
April 19, 2002 IAQ memo for Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406576
April 16, 2002 memo documenting IAQ measurements at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000410212
IAQ measurement report for Stuyvesant High School air quality.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336093
May 2002 IAQ measurements at Stuyvesant High School, BOE request.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406670
ATC field report documenting IAQ measurements at Stuyvesant High School.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000204475
ATC Associates memo reporting indoor air quality measurements collected at a New York City Board of Education school in April 2002.
Similarity score 0.995 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000372941
ATC provides IAQ test results for Stuyvesant High School (M477) on May 15, 2002.
Similarity score 0.995 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000372718
April 18, 2002 IAQ report for Stuyvesant High School.
Similarity score 0.995 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000406695
Indoor air quality measurements at Stuyvesant High School, May 2002, by ATC Associates for DOE.
Similar indexed content
NYC-WTC_000372830
Indoor air quality report for Stuyvesant High School dated May 2002.
Similar indexed content
NYC-WTC_000372941
ATC provides IAQ test results for Stuyvesant High School (M477) on May 15, 2002.
Similar indexed content
NYC-WTC_000270026
ATC IAQ measurements conducted March 15, 2002 at Stuyvesant High School for NYC BOE.
Similar indexed content
Report from ATC Associates detailing indoor air quality measurements collected at Stuyvesant High School on May 8, 2002.
Similar indexed content