Mr. Bernard P. Orlan February 12, 2002 Indoor Air Quality .Assessment Page 3 H.S. for Leadership & Pub. Serxhce (M894) ATC Project No. 15-19125-0290
Real-Time Environmental Measurements
ATC collected one hundred and forty (140) sets of real-time environmental measurements consisting of one hundred and thirty-four (134) in the school building and six (6) outdoors. All fourteen floors of the school were sunvyed. Field data sheets are found in the Attachment. Readings began at 8:00 A.M. and concluded after 3:40 P.M. The results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 65.2°F to 74.3'’F. Six (6) of the measurements were below the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature range was 36.9°F to 41.4°F.
Relative Humidity
The relative humidity indoors ranged from 22.5 percent to 47.2 percent. Sixty-six (66) measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. Tlie outdoor relative humidity range was 17.4 to 31.1 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 401 ppm to 1276 ppm. Five (5) of the measurements were: above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations ranged from 404 ppm to 432 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1132 ppm (background level + 700 ppm). The highest reading was recorded in Room 1406, occupied by 110 people at around 12:30 P.M. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 1 -2 ppm. These concentrations were below the NPAAQS/ASHRjVE guideline of 9 ppm. The outdoor CO concentrations were 1 -3 ppm.
Respirable Particulates (PM2_5)
Respirable particulate concentrations* indoors ranged between 2 pg/m^ to 21 pg/m^. None of the measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations ranged from 18 pg/m^ to 32 pg/m^ with an average of 25 pg/m^.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.
CITY_21MC100_006752168
NYC-WTC_000335386
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000376915
IAQ measurements report for M894 site at Trinity Place, BOE request.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335364
ATC IAQ measurements collected February 8, 2002 for the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000215155
Report summarizing indoor air quality measurements collected at a high school location in February 2002 to assess environmental conditions.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000377024
Indoor air quality measurements for High School for Leadership & [name].
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000377084
Correspondence reporting indoor air quality measurements at a NYC school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335434
ATC IAQ measurements collected February 14, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335327
ATC reports IAQ measurements collected February 5–6, 2002 for NYC BOE.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335345
ATC IAQ measurements conducted February 6, 2002 at the school.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370407
ATC IAQ measurements conducted March 4, 2002 at the referenced NYC BOE school.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000376933
IAQ report correspondence from ATC to NYC BOE for M894.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000215187
Report summarizing indoor air quality measurements collected at a high school location in late February 2002 to assess environmental conditions.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335550
Indoor air quality measurements collected at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000377024
Indoor air quality measurements for High School for Leadership & [name].
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000377122
Memo reporting indoor air quality measurements at a school site.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000376915
IAQ measurements report for M894 site at Trinity Place, BOE request.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370389
ATC Associates report of IAQ measurements at High School for Leadership & STEAM, 90 Trinity Place, Mar 1, 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335364
ATC IAQ measurements collected February 8, 2002 for the referenced school.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000377084
Correspondence reporting indoor air quality measurements at a NYC school.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000376915
IAQ measurements report for M894 site at Trinity Place, BOE request.
Similar indexed content
ATC IAQ measurements collected February 8, 2002 for the referenced school.
Similar indexed content
NYC-WTC_000215155
Report summarizing indoor air quality measurements collected at a high school location in February 2002 to assess environmental conditions.
Similar indexed content
NYC-WTC_000377024
Indoor air quality measurements for High School for Leadership & [name].
Similar indexed content
NYC-WTC_000377084
Correspondence reporting indoor air quality measurements at a NYC school.
Similar indexed content