Mr. Bernard P. Orlan May 8, 2002
Indoor Air Quality' Assessment Page 3
P.S.89M ATC Protect No. 15-19125-0297
Real-Time Environmental Measurements
ATC collected eighty (80) sets of real-time environmental measurements consisting of seventy-
one (71) from inside the school building and nine (9) from outdoors. All five floors of the school
building were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded at
approximately 11:30 A.M.
Temperature
Indoor diy bulb temperature measurements ranged from 67.3 °F to 74.8 °F. Forty-nine (49) of
the indoor measurements for temperature were below the range of 73 to 79°F (at 50 percent
relative humidity)-as recommended by the ASHRAE Standard 55-1992 during the summer
season . The outdoor temperature measurements ranged from 63.9°F to 65.0 °F.
Relative Humidity
The relative humidity indoors ranged from 39.8 to 54.0 percent. All indoor measurements for
relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for
occupant comfort. The outdoor relative humidity measurements ranged from 55.4 to 57.0
percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 427 ppm to 981 ppm. All indoor
measurements for CO2 were within the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The maximum outdoor (background)
CO2 concentration was 412 ppm. Therefore, the maximum acceptable level of CO2 at this
location was 1112 ppm (background level + 700 ppm). Levels above the recommended
maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator
of available outside makeup air. The primary source of CO2 indoors is occupant respiration.
The school building was occupied during ATC’s assessment.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged from 0 ppm to 1 ppm for all readings. These
concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO
concentration were 0 ppm for all collected readings.
Respirable Particulates (PM2,j)
Respirable particulate concentrations* indoors ranged between 11 pg/m^ to 24 pg/m^. The
average PM?.5 concentration for the entire school building was approximately 17 pg/m^. All of
the indoor measurements were below the NPAAQS of 65 .pg/m3 24-hour average concentration
of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA
recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor