Mr. Bernard P. Orlan May 8, 2002
Indoor Air Quality Assessment Page 2
P.S. S9M ATC Project No. 15-19125-0297
presented in this report should be used by the BOE as a guide to assess the need for further
improvements in current indoor air quality control activities.
EVALUATION CRITERIA
CuiTently, there are no regulator}^ standards for indoor air quality in non-industrial buildings,
such as offices and . schools. For the real-time data collected, ATC uses the commonly accepted
guidelines cited in the following publications:
Ventilation for Acceptable Indoor Air Quality (ASHEAE 62-1999), America.'n Society of
Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE);
Thennal Environmental Conditions for Human Occupancy (ASHRAE 55-1992);
Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American
Industrial Hygiene Association (AIHA).
Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation.
Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality
will be achieved at all times.
TABLEI
TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED
I ____________
Carbon Dioxide <700 parts per million (ppm) ASHRAE 62
(CO2) above background level
Carbon Monoxide 9 ppm ASHRAE 62 (adopted from
(CO) USEPA NPAAQS)
Respirable 65 micrograms per .cubic meter USEPA NPAAQS
Particulates (PM2.5) of air (qg/m^) 24-hour average
40 pg/m^ 24-hour average ' USEPA - Recommendation for
children / sensitive individuals
Temperature Summer: 73-79°F at 50% RH ASHRAE 55
Winter: 68-75°F at 50% RH
Relative Humidity 30-60 % ASHRAE55
Total Volatile
Organic Compounds 1 ppm AIHA
(TVOC)
USEPA = United States Environmental Protection Agency
NPAAQS = National Primary Ambient-Air Quality Standard
AIHA = American Industrial Hygiene Association