Mr. Bernard P. Orlan May 8, 2002
Indoor Air Quality Assessment Page 4
P. S. 89M ATC Prniect No. 15-101 25-0207
respirable particulate concentration measurements ranged from 29 to 34 pg/m^ with an average
of 31 pg/m3.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.
Type Concentrations
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC
concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment. ATC noted the following:
• The school building was occupied at the time of the assessment.
• No smoke odor was detected in the building
• The interior of the building appeared clean and free of dust and debris.
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of COp, CO and TVOCs were below applicable standards and guidelines.
2. Forty-nine (49). of the indoor measurements for temperature were below the range of 73 to
79°F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992
during the summer.
3. All indoor measurements for relative humidity were within the ASHRAE-recommended
range of 30 to 60 percent for occupant comfort.
4. All of the indoor respirable particulate measurements were below the NPAAQS of 65 pg/m^
24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic
diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals
and children.
It is our pleasure to provide these indoor air quality services to the New York City Board of
Education. If you have any questions about this report, please call (212) 353-8280, extension
211 or212.
Sincerely,
ATCASSOCIA TESINC.
Reviewed by:
LYIannis Efstathiou .Tames R. Cohn, CTH, CSP
Senior Project Manager Regional Manager, Industrial Hygiene Division