NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan May 7, 2002
Indoor Air Quality Assessment Page 3
P. S. 89M ATC Project No. 15-19125-0297
Real-Time Environmental Measurements
ATC collected eighty (80) sets of real-time environmental measurements consisting of sixty nine
(69) from inside the school building and eleven (11) from outdoors. All five floors of the school
building were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded at
approximately 11:30 A.M.
Temperature
Indoor dry bulb temperature measurements ranged from 69.5 °F to 75.0 °F. Twenty -three(23)
of the indoor measurements for temperature were below the range of 73 to 79°F (at 50 percent
relative humidity) as recommended by the ASHRAE Standard 55-1992 during the summer
season . The outdoor temperature measurements ranged from 58.1°F to 65.3 °F.
RelatiyeHumidify
The relative humidity indoors ranged from 36.3 to 45.2 percent. All indoor measurements for
relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for
occupant comfort. The outdoor relative humidity measurements ranged from 44.4 to 57.5
percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 554 ppm to 979 ppm. All indoor
measurements for CO2 were within the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The maximum outdoor (background)
CO2 concentration was 550 ppm. Therefore, the maximum acceptable level of CO2 at this
location was 1250 ppm (background level + 700 ppm). Levels above the recommended
maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator
of available outside makeup air. The primary source of CO2 indoors is occupant respiration.
The school building was occupied during ATC’s assessment.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 1 ppm for all readings. These concentrations
were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration were
also 2 ppm for all collected readings.
Respirable Particulates (PM2_i)
Respirable particulate concentrations* indoors ranged between 15 pg/m^ to 40 pg/m^. The
average PM2.5 concentration for the entire school building was approximately 30g/m3. All of
the indoor measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration
of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA
recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor