Mr..fiernard P. Orlan Indoor Air Quality Assessment ■ Pag® 3 P.S.89M ATC Protect No. 15-19125-0297 Real-Time Environmental Measurements
ATC collected eighty (80) sets of real-time environmental measurements consisting of eight (8) outdoors and thirty-two (32) inside in the morning (A.M.) .and the same number of readings in the afternoon (P.M.). All five floors of the school were surveyed:. The field data sheets are found in the Attachment. Readings began at 8:05 A.M. and concluded after 4:00 P.M. The results are described below:
Temperature
Indoor dry bulb temperature measurements ranged from 63.5°F to 75.3°F (A.M.) and 66.9°F to 73.0°F (PM). In the morning, two (2) measurements were above and six (6) were below the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55- 1992 during the heating season (wintertime conditions) while in the afternoon seven (7) measurements were below the same recommended range. The average outdoor temperature was 39.7°F (A.M.) and 52.9°F (P.M.).
Re!ative Humiciity
The relative humidity indoors ranged from 15.4 to 25.4 percent (A.M.) and 26.5 to 37.1 percent (P.M.). Fifteen (15) measurements collected in the afternoon were within the ASHRAE- recommended range of 30 to 60 percent for occupant comfort. All other readings were below the recommended range. The outdoor relative humidity averaged 42.3 percent (A.M.) and'36.0 percent (P.M.).
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 520 to 1019 ppm (A.M.) and 535 to 999 ppm (P.M.). All. CO2 measurements collected were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations averaged 494 ppm (A.M.) and 537 ppm (P.M.). Therefore, the maximum acceptable level of CO2 at this location was 1237 ppm (background level + 700 ppm). The highest indoor level was measured in Classroom 504. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration. The 2'^3 and 3 *’3 floors of the school building were not occupied during AFC’s assessment.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged from 0 to 1 ppm. These concentrations were below the ASHRAE guideline of 9 ppm. The outdoor CO concentration was 0 ppm.
Respirable Particulates TPAp
Respirable particulate concentrations* indoors ranged from 21 pg/m^ to 42 pg/m3 (A.M.) and 30 pg/m3 to 78 pg/m^ (P.M.). Six indoor measurements collected in the afternoon were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PM2.5 concentration* for the entire school
CITY_21MC100_003270822
NYC-WTC_000327376
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000382575
Indoor air quality measurements collected Feb 7, 2002 at P.S. 89M.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000185979
Report from ATC Associates detailing indoor air quality measurements collected at PS 89M for the Board of Education.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000327350
ATC IAQ report for the NYC Board of Education; measurements to assess air quality before occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000382559
Indoor air quality evaluation at P.S. 89M, Feb 2002.
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000274646
Indoor air quality measurements collected Feb 14, 2002 for P.S. 89M.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000404383
Report of indoor air quality measurements at PS 89M.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000404315
ATC IAQ measurements at PS 89M requested by NYC BOE; report with findings.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000274586
LIAQ measurements at P.S. 89M to evaluate air quality before building re-occupancy, Feb 2002.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000382571
Indoor air quality measurements collected Feb 6, 2002 at P.S. 89M.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000185967
Report from ATC Associates detailing indoor air quality measurements collected at PS 89M for the Board of Education.
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000327362
ATC memo noting IAQ measurements at a NYC school requested before re-occupancy.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000382619
Report of indoor air quality measurements at P.S. 89M requested before re-occupancy.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000404371
Indoor air quality measurements collected for PS 89M re-occupancy prep.
Similarity score 0.993 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000274586
LIAQ measurements at P.S. 89M to evaluate air quality before building re-occupancy, Feb 2002.
Similarity score 0.993 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000382571
Indoor air quality measurements collected Feb 6, 2002 at P.S. 89M.
Similarity score 0.993 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000404347
ATC IAQ measurements at P.S. 89M for pre-occupancy assessment.
Similarity score 0.993 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000185979
Report from ATC Associates detailing indoor air quality measurements collected at PS 89M for the Board of Education.
Similarity score 0.993 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000274646
Indoor air quality measurements collected Feb 14, 2002 for P.S. 89M.
Similarity score 0.993 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000382575
Indoor air quality measurements collected Feb 7, 2002 at P.S. 89M.
Similar indexed content
NYC-WTC_000185979
Report from ATC Associates detailing indoor air quality measurements collected at PS 89M for the Board of Education.
Similar indexed content
NYC-WTC_000327350
ATC IAQ report for the NYC Board of Education; measurements to assess air quality before occupancy.
Similar indexed content
NYC-WTC_000382559
Indoor air quality evaluation at P.S. 89M, Feb 2002.
Similar indexed content
NYC-WTC_000274646
Indoor air quality measurements collected Feb 14, 2002 for P.S. 89M.
Similar indexed content