Mr. Bernard P. Orian October 16, 2001 Indoor .Air Quality Assessment Page 3 P.S. 130M (Manhattan) ATC Proieci No. 15-19125-0276
SAMPLING RESULTS
Real-Time Environmental Measurements
ATC collected fifty (50) sets of real-time environmental measurements consisting of forty-nine (49) in the school building and one (1) outdoors. These results are described below. Field data sheets are found in Attachment 1.
Temperature
Indoor diy bulb temperature measurements ranged from 72.3 °F to 76.7 .^°F. Five (5) measurements were slightly above the range of 69 to 76°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). These readings were on the 2nd floor. The deviations were less than 1 °F and are not significant. The outdoor temperature was 69.7 °F.
Relative Humidity
The relative humidity indoors ranged from 49.0 percent to 54.8 percent. All measurements were within ASHRAE’s recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity was 51.1 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 406 ppm to 769 ppm. All CO? measurements were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 360 ppm. Therefore, the acceptable level of CO2 at this location was 1060 ppm (background level + 700 ppm). Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentraiion was also 0 ppm.
Respirable Particulates
Respirable particulate concentrations indoors ranged between 12 pg/m^ and 29 pg/m3. All concentrations were below the NPAAQS/ASHRAE guideline of 50 pg.'m-’ (annual average concentration of particulate matter 10 micrometers or less in aerodynamic diameter). The outdoor respirable particulate concentration was 35 pg/m-’.
CITY_21MC100_003267116
NYC-WTC_000324059
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000329843
IAQ assessment report for PS 130M school building.
12 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311732
Indoor air quality assessment conducted October 12, 2001 at Stuyvesant High School.
10 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000313593
ATC measures temperature and basic IAQ parameters at PS 89M for BOE in May 2002.
10 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311748
IAQ assessment report for Stuyvesant High School dated October 15, 2001.
11 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000292885
IAQ field report for Stuyvesant High School dated Oct 16, 2001.
11 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000373529
Indoor air quality report for P.S. 234M, January 22, 2002.
10 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311687
Indoor air quality assessment conducted on October 9, 2001 at Stuyvesant High School.
10 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000328348
ATC reports indoor air quality measurements at P.S. 89M per BOE request.
10 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397271
IAQ measurements report for PS 234M, Apr 2002.
9 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000313556
Indoor air quality measurements collected at PS 89M for BOE.
10 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311704
Indoor air quality assessment conducted on October 10, 2001 at Stuyvesant High School.
11 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000199187
Letter from ATC Associates reporting indoor air quality measurements collected at P.S. 234M on April 11, 2002.
9 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000329843
IAQ assessment report for PS 130M school building.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271114
Indoor air quality assessment conducted at Stuyvesant High School.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000371814
ATC report of IAQ measurements conducted April 9, 2002 at P.S. 234M for BOE review.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000314791
Indoor air quality measurements at PS 234M; March 22, 2002.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000314801
ATC report of IAQ measurements conducted March 21, 2002 at PS 234M for BOE.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271099
Indoor air quality assessment results for Stuyvesant HS dated Oct 12, 2001.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000329843
IAQ assessment report for PS 130M school building.
Similar indexed content
NYC-WTC_000311732
Indoor air quality assessment conducted October 12, 2001 at Stuyvesant High School.
Similar indexed content
NYC-WTC_000313593
ATC measures temperature and basic IAQ parameters at PS 89M for BOE in May 2002.
Similar indexed content
NYC-WTC_000311748
IAQ assessment report for Stuyvesant High School dated October 15, 2001.
Similar indexed content
IAQ field report for Stuyvesant High School dated Oct 16, 2001.
Similar indexed content