Indoor air quality measurements at PS 234M; March 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗ATC report of IAQ measurements conducted March 21, 2002 at PS 234M for BOE.
NYC-WTC_000314801–000314804OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan March 22, 2002 Indoor Air Quality Assessment Page 3 P. S. 234M ATC Project No. 15-19125-0279
REAL-TIME ENVIRONMENTAL MEASUREMENTS
ATC collected sixty (60) sets of real-time environmental measurements consisting of fifty'-one (51) from inside the school building and nine (9) outdoors. All three floors of the school were surveyed. These results are described below.
Field data sheets are found m Attachment 1. Readings began at 12:00 P.M. and concluded after 2:05 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 67.0 °F to 80.3 °F. Eighteen (18) indoor measurements for temperature were above and one (1) was below the range of 68 to 75°F (at 50 percent relative humidity) as recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature measurements ranged from 48.6 to 56.8 °F.
Relative Humidity
The relative,humidity indoors ranged from 19.0. percent to 28.6 percent. All of the indoor measurements for relative humidity were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 23.0 to 24.9 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 465 ppm to 963 ppm. All of the measurements were within the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 421 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1121 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were between 0 ppm to 1 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were 0 ppm.
Respirable Particulates (PM2,j)
Respirable particulate concentrations* indoors ranged between 16 pg/m^ to 48 ng m-\ None
CITY_21MC100_003032015
NYC-WTC_000314803
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000381416
Indoor air quality measurements at PS 234M; March 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000294472
Indoor air quality measurements at PS 234M, documenting March 22, 2002 activities.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000314815
IAQ measurements collected March 19, 2002 at PS 234M for BOE.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000294428
Careful IAQ measurements at PS 234M, dated March 14, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000314825
IAQ measurements collected March 18, 2002 at PS 234M for BOE.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000314985
Indoor air quality measurements collected at P.S. 234M.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000294458
Indoor air quality measurements at PS 234M, prepared for NYC BOE, March 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397261
IAQ measurements report for PS 234M; April 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000314964
Indoor air quality measurements collected at P.S. 234M for BOE.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000314954
Air quality measurements collected at P.S. 234M for BOE.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000294438
ATC IAQ report for PS 234M, measurements collected March 18, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000314989
INS IAQ measurements collected at P.S. 234M; BOE referenced.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000381416
Indoor air quality measurements at PS 234M; March 2002.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000314825
IAQ measurements collected March 18, 2002 at PS 234M for BOE.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000381436
Indoor air quality measurements at PS 234M; March 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000294472
Indoor air quality measurements at PS 234M, documenting March 22, 2002 activities.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000314791
Indoor air quality measurements at PS 234M; March 22, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000314985
Indoor air quality measurements collected at P.S. 234M.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000381416
Indoor air quality measurements at PS 234M; March 2002.
Similar indexed content
NYC-WTC_000294472
Indoor air quality measurements at PS 234M, documenting March 22, 2002 activities.
Similar indexed content
NYC-WTC_000314815
IAQ measurements collected March 19, 2002 at PS 234M for BOE.
Similar indexed content
NYC-WTC_000294428
Careful IAQ measurements at PS 234M, dated March 14, 2002.
Similar indexed content
NYC-WTC_000314825
IAQ measurements collected March 18, 2002 at PS 234M for BOE.
Similar indexed content