Mr. Bernard P. Orlan March 22, 2002 Indoor Air Quality Assessment Page 4 P. S. 234M ATC Project No. 15-19125-0279

of the indoor or outdoor measurements for PM2.5 were above the NPAAQS of 65 pg/m^ 24- hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. One (1) of the indoor and four (4) outdoor measurements were above the USEPA recommended concentration of 40 pg/m^ recommended for sensitive individuals and children The average PM2.5 concentration for the entire school building was approximately 27 pg/m^. The outdoor respirable particulate concentration ranged from 39 to 50 pg/m^ with an average of 42 pg/m^.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average. TVOCConcentration

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm. OBSERVATIONS During this assessment, ATC noted the following: • The building was occupied at the time of the assessment; • No smoke odor was detected in the building.

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Concentrations of CO ,CO2and TVOCs were within applicable standards and guidelines. 2. Eighteen (18) indoor measurements for temperature were above and one (1) was below the range of-68 to 75°F (at 50 percent relative humidity) as recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). 3. All of the indoor measurements for relative humidity were below the ASHRAE- recommended range of 30 to 60 percent for occupant comfort. 4. None of the indoor or outdoor measurements for PM2.5 were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. One (1) of the indoor and four (4) outdoor measurements were above the USEPA recommended concentration of 40 pg/m^ recommended for sensitive individuals and children. It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, extension 211 or 212.

Sincerely, A TC ASSOCIA TES INC.

Yiannis Efstathiou Senior Project Manager

Attachment

CITY_21MC100_003032016

NYC-WTC_000314804

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000314804Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →