Mr. Bernard P. Orlan March 19, 2002 Indoor Air Quality Assessment Page 3 P. S. 234M ATC Project No. 15-19125-0279

Real-Time Environmental Measurements

ATC collected sixty (60) sets of real-time environmental measurements consisting of fifty-one (51) from inside the school building and nine (9) outdoors. All three floors of the school were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 11:55 A.M. and concluded after 1:55 P.M.

Temperature

Indoor dry bulb temperature measurements ranged from 64.2 °F to 73.0 °F. One (1) indoor measurement for temperature was below the range of 68 to 75°F (at 50 percent relative humidity) as recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature measurements ranged from 37.6 to 39.0 °F.

Relative Humidity

The relative humidity indoors ranged from 28.0 percent to 35.2 percent. Twenty-five (25) of the indoor measurements for relative humidity were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 49.6 to 52.8 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 494 ppm to 925 ppm. All of the measurements were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 494 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1194 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors ranged fromO ppm to 2 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 1 to 2 ppm.

Respirable Particulates (PM2,5)

Respirable particulate concentrations* indoors ranged between 7 pg/m^ to 19 pg/m^, None of the indoor or outdoor measurements for PM2.5 were above the NPAAQS of 65 pg/m^ 24- hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Also none of the measurements were above the USEPA recommended concentration of 40 pg/m3 for sensitive individuals and children.

CITY_21MC100_003032048

NYC-WTC_000314827

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000314827Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →