Mr. Bernard P. Orlan October 16, 2001 Indoor Air Quality Assessment Page 4 P.S. 130M (Manhattan! ATC Project No. 15-19125-0276

TVOC Concentration

TVOC concentrations indoors were 0.0 ppm for all readings. These concentrations were below the AIHA guideline of 1 ppm for non-industrial buildings. The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

Dunng this asses.sment, ATC noted the following: • All the windows in the building were closed, except for windows in 'Rooms 202 & 511; • The interior of the building appeared clean and free of dust and debris: • The building was occupied at the time of the assessment; ( • No odor was detected in the school building during ATC’s site visit.

FINDINGS

Based on the visual inspection of the occupied spaces and real-time measurements, the following findings are presented;

1. Measurements of relative humidity and concentrations of CO, CO2, TVOCs and respirable particulates were within applicable standards and guidelines.

2. Five temperature measurements, on the floor, were slightly above the range recommended by ASHRAF 55-1992.

CONCLUSION

Based on our observations and measurements, ATC concludes that the assessed locations were suitable for occupancy at the time of ATC’s investigation. Some individuals may find the temperature in some rooms to be uncomfortable.

RECOMMENDATIONS

Based on the findings and conclusions above, ATC recommends the following;

• Keep temperature within established guidelines by using adequate ventilation: ! • Conduct timely follow-up monitoring/inspection to ensure that recommendations were effective.

CITY_21MC100_003267117

NYC-WTC_000324060

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000324060Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000292885

IAQ field report for Stuyvesant High School dated Oct 16, 2001.

Similar indexed content

Compare copies and versions →