Mr. Bernard P. Orlan October 16, 2001 Indoor’Air Quality Assessment Page 3 P.S. 130M (Manhattan) ATC Project No. 15-19125-0276

SAMPLING RESULTS

Real-Time Environmental Measurements

ATC collected fifty (50) sets of real-time environmental measurements consisting of forty-nine (49) in the school building and one (1) outdoors. These results are described below. Field data sheets are found in Attachment 1.

Temperature

Indoor dry bulb temperature measurements ranged from 72.3 °F to 76.7 °F. Five (5) measurements were slightly above the range of 69 to 76°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). These readings were on the 2nd floor. The deviations were less than TF and are not significant. The outdoor temperature was 69.7 °F.

Relative Humidity

The relative humidity indoors ranged from 49.0 percent to 54.8 percent. All measurements were within ASHRAE’s recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity was 51.1 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 406 ppm to 769 ppm. All CO? measurements were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) COg concentration was 360 ppm. Therefore, the acceptable level of CO2 at this location was 1060 ppm (background level + 700 ppm). Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO? indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was also 0 ppm.

Respirable Particulates

Respirable particulate concentrations indoors ranged between 12 pg/m^ and 29 pg/m^. All concentrations were below the NPAAQS/ASHRAE guideline of 50 pg/m3 (annual average concentration of particulate matter 10 micrometers or less in aerodynamic diameter). The outdoor respirable particulate concentration was 35 pg/m^.

CITY_21MC100_003273838

NYC-WTC_000329845

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000329845Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000292885

IAQ field report for Stuyvesant High School dated Oct 16, 2001.

Similar indexed content

Compare copies and versions →