Mr. Bernard P, (.Irian November 18. 2001 Indoor Air (Quality Assessment Page 2 .S1 iivvcsaut High School (M477) ATC Project No. 15-19125-0246

presented in this report should be used by the IBOE as a guide to assess the need for further improvements in current indoor air quality control activities.

EVAIJJATION CRITERIA

Currently, there are no regulatory standards for indoor tor quality in noil-industrial buildings, such as offices and schools. For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications:

Pentildlion fi)i- Acce/fPihle Indoor Air Qiicility fASHR.4E 62-!9Q9), American Society of Heating, Refrigerating, and Air-Conditioning Engineer.s (ASHRAE); Theriinil Emironiiicntal Conditions for Huiniin Occupancy (ASHRAE 55,-1992): Indiisiriol Hygienists Guide Io Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA).

Table I lists target guidelines for the parameters that ATC evaluated during this investigation. Meeting one. some, or all of the li.sted values does not assure that acceptable indoor air quality will be achieved at all times.

TABLE 1 TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED

I’ARAMEIER TARGET LEVEL AGENCY OR ORGANIZATION Respirable 6,5 micrograms per cubic meter USEPA NPAAQS Particulates (PMg.b) of air (ug/m^) 24-hour average Total Volatile 1 ppm Organic Compounds AI HA (TVOC) USEPA United States Environmental Protection Agency NPAAQS = National Primary Ambient-Air Quality Standard AIHA = American Industrial Hygiene Association

Real-Time Env iron m e ntaiJVI easlire m en i s

ATC collected one hundred and sixty-eight (168) sets of real-time environmental measurements consisting of one hundred and sixty-seven (167) in the school building and one (1) outdoors. All seven fioors of the school were surveyed. These results are described below. Field data sheets are found in Attachment 1.

Re.spirab/e Pdr/iailcile.s (PM?

Respirable particulate concentrations* indoors ranged between 11 pg/nC to 19 pg/mJ with an m eriige of approximately 14 pg'nC. All mea.surements were below the NPAAQS of 65 pg/nV 24-hoiir average conCenlration of particulate matter 2.5 micrometers or less in aerodvnamic diameter. I he outdoor respirable particulate concentration wa.s 47 pg/nv’.

CITy_21MC100_011274319

NYC-WTC_000323936

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000323936Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →