ATC Associates is pleased to provide this report of an indoor air quality assessment.
9 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗ATC Associates report of IAQ assessment at the referenced school in NYC.
NYC-WTC_000323935–000323938OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr. Bernard P, (.Irian November 18. 2001 Indoor Air (Quality Assessment Page 2 .S1 iivvcsaut High School (M477) ATC Project No. 15-19125-0246
presented in this report should be used by the IBOE as a guide to assess the need for further improvements in current indoor air quality control activities.
EVAIJJATION CRITERIA
Currently, there are no regulatory standards for indoor tor quality in noil-industrial buildings, such as offices and schools. For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications:
Pentildlion fi)i- Acce/fPihle Indoor Air Qiicility fASHR.4E 62-!9Q9), American Society of Heating, Refrigerating, and Air-Conditioning Engineer.s (ASHRAE); Theriinil Emironiiicntal Conditions for Huiniin Occupancy (ASHRAE 55,-1992): Indiisiriol Hygienists Guide Io Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA).
Table I lists target guidelines for the parameters that ATC evaluated during this investigation. Meeting one. some, or all of the li.sted values does not assure that acceptable indoor air quality will be achieved at all times.
TABLE 1 TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED
I’ARAMEIER TARGET LEVEL AGENCY OR ORGANIZATION Respirable 6,5 micrograms per cubic meter USEPA NPAAQS Particulates (PMg.b) of air (ug/m^) 24-hour average Total Volatile 1 ppm Organic Compounds AI HA (TVOC) USEPA United States Environmental Protection Agency NPAAQS = National Primary Ambient-Air Quality Standard AIHA = American Industrial Hygiene Association
Real-Time Env iron m e ntaiJVI easlire m en i s
ATC collected one hundred and sixty-eight (168) sets of real-time environmental measurements consisting of one hundred and sixty-seven (167) in the school building and one (1) outdoors. All seven fioors of the school were surveyed. These results are described below. Field data sheets are found in Attachment 1.
Re.spirab/e Pdr/iailcile.s (PM?
Respirable particulate concentrations* indoors ranged between 11 pg/nC to 19 pg/mJ with an m eriige of approximately 14 pg'nC. All mea.surements were below the NPAAQS of 65 pg/nV 24-hoiir average conCenlration of particulate matter 2.5 micrometers or less in aerodvnamic diameter. I he outdoor respirable particulate concentration wa.s 47 pg/nv’.
CITy_21MC100_011274319
NYC-WTC_000323936
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000323931
ATC Associates is pleased to provide this report of an indoor air quality assessment.
9 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000323919
ATC Associates indoor air quality assessment at a NYC school in mid-November 2001.
9 shared non-person entities · 1 shared topics · similarity 0.987
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000323925
ATC Associates indoor air quality assessment at a NYC school on Nov 16, 2001.
8 shared non-person entities · 1 shared topics · similarity 0.985
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000323908
ATC Associates indoor air quality assessment at a New York City school on Nov 15, 2001.
9 shared non-person entities · 1 shared topics · similarity 0.984
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000323939
ATC Associates IAQ assessment report for the school in New York City.
9 shared non-person entities · 1 shared topics · similarity 0.983
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291841
Indoor air quality measurements report for 90 Trinity Place, May 2002.
8 shared non-person entities · 1 shared topics · similarity 0.982
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000229818
IAQ assessment at PS 234M, Nov 2001; indoor air quality report by ATC Associates.
6 shared non-person entities · 1 shared topics · similarity 0.977
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000330290
ATC IAQ assessment conducted at a NYC school, with findings for IAQ conditions.
8 shared non-person entities · 1 shared topics · similarity 0.977
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000236945
Report of indoor air quality measurements collected on January 24, 2002, at P.S. 89M.
8 shared non-person entities · 1 shared topics · similarity 0.982
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000236977
Letter from ATC Associates to NYC Board of Education reporting indoor air quality measurements at P.S. 89M collected on January 18, 2002.
8 shared non-person entities · 1 shared topics · similarity 0.981
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000236967
Letter from ATC Associates to NYC Board of Education reporting indoor air quality measurements at P.S. 89M collected on January 18, 2002.
8 shared non-person entities · 1 shared topics · similarity 0.980
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000236953
Letter from ATC Associates to NYC Board of Education reporting indoor air quality measurements at P.S. 89M collected on January 18, 2002.
8 shared non-person entities · 1 shared topics · similarity 0.979
machine-extracted · confidence unavailable · Check page ↗Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000330290
ATC IAQ assessment conducted at a NYC school, with findings for IAQ conditions.
Similarity score 0.992 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000312114
ATC memo accompanying IAQ measurements for Stuyvesant High School conducted mid-November 2001.
Similarity score 0.990 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000312138
ATC memo for indoor air quality measurements at Stuyvesant High School on Nov 18, 2001.
Similarity score 0.990 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000330311
IAQ assessment summary for a NYC school, with project number 19125-0286.
Similarity score 0.988 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000256115
Report of respirable particulate measurements at a NYC public school (Feb 2002).
Similarity score 0.988 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000323931
ATC Associates is pleased to provide this report of an indoor air quality assessment.
Similarity score 0.987 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000323931
ATC Associates is pleased to provide this report of an indoor air quality assessment.
Similar indexed content
NYC-WTC_000323919
ATC Associates indoor air quality assessment at a NYC school in mid-November 2001.
Similar indexed content
NYC-WTC_000323925
ATC Associates indoor air quality assessment at a NYC school on Nov 16, 2001.
Similar indexed content
NYC-WTC_000323908
ATC Associates indoor air quality assessment at a New York City school on Nov 15, 2001.
Similar indexed content
NYC-WTC_000323939
ATC Associates IAQ assessment report for the school in New York City.
Similar indexed content