Mr. Bernard P. Orlan November 18. 2001 Indoor Air Quality Assessment Page 2 Stuvvesant High School (MA??) ATC Project No. 15-19125-0246
presented in this report should be used by the BOE as a guide to assess the need for further improvements in current indoor air quality control activities.
EVALUATION CRITERIA
Currently, there are no regulatory standards for indoor air quality in non-industrial buildings, such as offices and schools. For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications:
Ventilation for Acceptable Indoor Air Oualit)j (ASHRAE 62-1999), American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE); Thermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992); IndustJ'ial Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA).
Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation. Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality will be achieved at all times.
TABLEI TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED
PARAMETER TARGET LEVEL AGENCY OR ORG.ANIZATION Respirable 65 micrograms per cubic meter USEPA NPAAQS Particulates (PM2.5) of air (pg/m^) 24-hour average Total Volatile 1 ppm Organic Compounds AIHA (TVOC) USEPA = United States Environmental Protection Agency AIHA = American Industrial Hygiene Association
Real-Time Environmental Measurements
ATC collected one hundred and ninety-two (192) sets of real-time environmental measurements consisting of one hundred and ninety (190) in the school building and two (2) outdoors. All ten floors of the school were surveyed. These results are described below. Field data sheets are found in Attachment 1.
Respirable Particiilafes (PM2.5)
Respirable particulate concentrations* indoors ranged between 9 gg/ml to 40 ug/m^. All measurements were below the NPAAQS of 65 pig/ml 24-hour average concentration of paniculate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations w'ere 27 and 32 jj.g/in-’.
The average PM2.5 concentration for the entire school building was approximately 18 ug/mA In addition to higher efficiency rating filters on their HVAC units, portable High Efficiency
CITY_21MC1OO_OO3O46O13
NYC-WTC_000312139
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000312114
ATC memo accompanying IAQ measurements for Stuyvesant High School conducted mid-November 2001.
13 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000330290
ATC IAQ assessment conducted at a NYC school, with findings for IAQ conditions.
10 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000330311
IAQ assessment summary for a NYC school, with project number 19125-0286.
12 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000312263
Cover letter for lAQ report at Stuyvesant High School.
13 shared non-person entities · 1 shared topics · similarity 0.987
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000312060
ATC IAQ assessment conducted at Stuyvesant High School on November 14, 2001.
13 shared non-person entities · 1 shared topics · similarity 0.985
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000197574
Letter from ATC Associates reporting indoor air quality measurements collected at a Board of Education school in November 2001.
13 shared non-person entities · 1 shared topics · similarity 0.985
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271345
Letter from ATC to BOE about IAQ assessment at Stuyvesant High School, Nov 13, 2001.
13 shared non-person entities · 1 shared topics · similarity 0.985
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311979
Nov 7, 2001 memo documenting IAQ assessment at Stuyvesant High School.
13 shared non-person entities · 1 shared topics · similarity 0.985
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000312040
Nov 14, 2001 memo relating to IAQ assessment at Stuyvesant High School.
13 shared non-person entities · 1 shared topics · similarity 0.985
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000312163
ATC memo summarizing indoor air quality measurements at Stuyvesant High School, November 2001.
12 shared non-person entities · 1 shared topics · similarity 0.985
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000312017
Nov 9, 2001 memo regarding IAQ assessment at Stuyvesant High School.
13 shared non-person entities · 1 shared topics · similarity 0.984
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311998
Nov 8, 2001 memo re: IAQ assessment at Stuyvesant High School (M477).
13 shared non-person entities · 1 shared topics · similarity 0.984
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000330290
ATC IAQ assessment conducted at a NYC school, with findings for IAQ conditions.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000312114
ATC memo accompanying IAQ measurements for Stuyvesant High School conducted mid-November 2001.
Similarity score 0.995 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000330311
IAQ assessment summary for a NYC school, with project number 19125-0286.
Similarity score 0.995 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000256115
Report of respirable particulate measurements at a NYC public school (Feb 2002).
Similarity score 0.993 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000256103
ATC memo reporting respirable particulate measurements at Stuyvesant High School (Feb 19, 2002).
Similarity score 0.992 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000256127
Report of respirable particulate measurements collected at Stuyvesant High School.
Similarity score 0.992 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000312114
ATC memo accompanying IAQ measurements for Stuyvesant High School conducted mid-November 2001.
Similar indexed content
NYC-WTC_000330290
ATC IAQ assessment conducted at a NYC school, with findings for IAQ conditions.
Similar indexed content
NYC-WTC_000330311
IAQ assessment summary for a NYC school, with project number 19125-0286.
Similar indexed content
NYC-WTC_000312263
Cover letter for lAQ report at Stuyvesant High School.
Similar indexed content
NYC-WTC_000312060
ATC IAQ assessment conducted at Stuyvesant High School on November 14, 2001.
Similar indexed content