Mr. Bernard P. Orlan November 17, 2001 ’ Indoor Air Quality Assessment Page 2 Stuvvesant High School (M477) ATC Project No. 15-19125-0246
presented in this report should be used by the BOE as a guide to assess the need for further improvements in current indoor air quality control activities.
EVALUATION CRITERIA
Currently, there are no regulatory standards for indoor air quality in non-industrial buildings, such as offices and schools. For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications:
Ventilation for Acceptable Indoor Air Quality (ASHRAE 62-1999), American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE); Thermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992): Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA).
Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation. Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality will be achieved at all times.
TABLE I TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED
PARAMETER TARGET LEVEL AGENCY OR ORGANIZATION Respirable 65 micrograms per cubic meter USEPA NPAAQS Particulates (PM2,5) of air (pg/m^) 24-hour average Total Volatile 1 ppm Organic Compounds AIHA (TVOC) USEPA = United States Environmental Protection Agency NPAAQS = National Primary Ambient-Air Quality Standard AIHA = American Industrial Hygiene Association
Real-Time Environmental Measurements
ATC collected one hundred and fifty-nine (159) sets of real-time environmental measurements consisting of one hundred and fifty-eight (158) in the school building and one (1) outdoors. All seven floors of the school were surveyed. These results are described below. Field data sheets are found in Attachment 1.
Respirable Particulates (PM2 5)
Respirable particulate concentrations* indoors ranged between 8 pg/m^ to 18 pg/m^ with an average of approximately 10 pg/m^. All measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentration was 24 pg/m^.
CITY_21MC1OO_OO3275O32
NYC-WTC_000330291
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000330311
IAQ assessment summary for a NYC school, with project number 19125-0286.
11 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000312138
ATC memo for indoor air quality measurements at Stuyvesant High School on Nov 18, 2001.
10 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000312114
ATC memo accompanying IAQ measurements for Stuyvesant High School conducted mid-November 2001.
10 shared non-person entities · 1 shared topics · similarity 0.993
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311979
Nov 7, 2001 memo documenting IAQ assessment at Stuyvesant High School.
10 shared non-person entities · 1 shared topics · similarity 0.989
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000330258
November 15, 2001 IAQ assessment report to NYC Board of Education.
11 shared non-person entities · 1 shared topics · similarity 0.989
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271149
Indoor air quality assessment conducted on Oct 18, 2001 at Stuyvesant HS.
10 shared non-person entities · 1 shared topics · similarity 0.988
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000188540
Report detailing an indoor air quality assessment conducted at a school on Chambers Street on October 25, 2001.
10 shared non-person entities · 1 shared topics · similarity 0.988
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311846
ATC letter enclosing IAQ assessment results for Stuyvesant HS.
9 shared non-person entities · 1 shared topics · similarity 0.988
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000293077
Indoor air quality assessment conducted at Stuyvesant High School on Nov 2, 2001 for NYC Board of Education.
10 shared non-person entities · 1 shared topics · similarity 0.988
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311960
Nov 6, 2001 memo regarding IAQ assessment at Stuyvesant High School for BOE.
10 shared non-person entities · 1 shared topics · similarity 0.988
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271280
Memo reporting indoor air quality assessment at Stuyvesant High School, Nov 2001.
10 shared non-person entities · 1 shared topics · similarity 0.987
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271298
Memo stating IAQ assessment conducted at Stuyvesant HS, Nov 2001.
10 shared non-person entities · 1 shared topics · similarity 0.987
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000312138
ATC memo for indoor air quality measurements at Stuyvesant High School on Nov 18, 2001.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000330311
IAQ assessment summary for a NYC school, with project number 19125-0286.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000312114
ATC memo accompanying IAQ measurements for Stuyvesant High School conducted mid-November 2001.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000256115
Report of respirable particulate measurements at a NYC public school (Feb 2002).
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000372680
April 11, 2002 indoor air quality report for Stuyvesant High School.
Similarity score 0.993 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000256103
ATC memo reporting respirable particulate measurements at Stuyvesant High School (Feb 19, 2002).
Similarity score 0.993 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000330311
IAQ assessment summary for a NYC school, with project number 19125-0286.
Similar indexed content
NYC-WTC_000312138
ATC memo for indoor air quality measurements at Stuyvesant High School on Nov 18, 2001.
Similar indexed content
NYC-WTC_000312114
ATC memo accompanying IAQ measurements for Stuyvesant High School conducted mid-November 2001.
Similar indexed content
NYC-WTC_000311979
Nov 7, 2001 memo documenting IAQ assessment at Stuyvesant High School.
Similar indexed content
NYC-WTC_000330258
November 15, 2001 IAQ assessment report to NYC Board of Education.
Similar indexed content