NYC 9/11 Public Portal Document 104 East 25th Strest 10th FL New York, New York 10010 www.3tc-enviro.com 212.3538280 Fax 212.353.8306 ASSOCIATES INC.

November 19, 2001

Mr. Bernard P. Orlan Director, Environmental Health & Safety New York City Board of Education 28-1 I Queens Plaza North Long Island City, NY 11101-4008

Re; Indoor Air Quality Assessment Murray Bergtraum HS (M520) 411 Pearl Street New York, New York 10038 ATC Project No. 15-19125-0286

Dear Mr. Orlan:

ATC Associates Inc. (ATC) is pleased to provide this report of an indoor air quality (lAQ) assessment conducted on November 17, 2001, at the referenced school. The New York City Board of Education (BOE) requested this assessment to determine if acceptable indoor air quality is being maintained.

SCOPE OF WORK

As per your request, ATC conducted this evaluation to assess total volatile organic compounds (TVOCs) and respirable particulates.

Tenzin Namgyal and Wagdi Abdelshahid, Industrial Hygienists, of ATC’s New York City office, conducted the assessment. ATC’s findings and conclusions are based on a visual inspection, real-time environmental measurements and conditions present in the school at the time of the assessment.

ATC measured concentrations of respirable particulates with a Dust-Trak® Aerosol Monitor Model 8520, manufactured by TSI, Inc.

ATC measured concentrations of TVOCs using a RAE Systems, Inc. MiniRAE® photoionization detector (PID).

The assessment was performed consistent with generally accepted indoor air quality assessment practices. As with all such assessments, there were inherent limitations created by constraints of time, operational and work practice variability, variations in indoor air quality parameters and sampling and analytical accuracy. The results of the sampling represent conditions found on the dates of the survey and may not represent conditions found at other times. The information

CITY_21MC100_003275031

NYC-WTC_000330290

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000330290Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

IAQ memo, Stuyvesant HS, 2001

NYC-WTC_000312138

ATC memo for indoor air quality measurements at Stuyvesant High School on Nov 18, 2001.

Similar indexed content

IAQ memo, Stuyvesant HS, Nov 2001

NYC-WTC_000312114

ATC memo accompanying IAQ measurements for Stuyvesant High School conducted mid-November 2001.

Similar indexed content

Compare copies and versions →