ATC Associates is pleased to provide this report of an indoor air quality assessment.

NYC-WTC_000323931–000323934
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan November 17. 2001 ’ Indoor Air (duality Assessment Page 2 Stiivvcsant Hitih School (M477) ATC Project No. 15-19125-0246

presented in this report should be used by the DOE as ;i guide to assess the need for further improvements in current indoor air quality control activities.

EVALUATION CRITERIA

Currently, there are no regulatory standards for indoor air quality in non-industrial buildings. such as offices and schools. For the real-time data collected. ATC uses the commonly accepted guidelines cited in the following publications:

IPnli/cilion for Acceptable Indoor Air Quality ('ASHRAE 62-1999), American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE); thermal Environmental Condition.yfor Human Occupancy (ASHRAE 5>-1992); Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA).

Table I lists target guidelines for the parameters that ATC evaluated during this investigation. Meeting one. some, or all of the listed values does not assure that acceptable indoor air quality w ill be achieved at all times.

TABLE 1 TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED

PARAMETER TARGET LEVEL AGENCY OR ORGANIZATION Respirable 65 micrograms per cubic meter USEPA NPAAQS Particulates (PM2.5) of air ((Lig/m-’) 24-hour average Total Volatile 1 ppm Organic Compounds Al HA (TVOC) USEPA United States Environmental Protection Agency NPAAQS = National Primary Ambient-Air Quality Standard AiHA = American Industrial Hygiene Association

Real-Time Envi ronmental Measurements

ATC collected one hundred and fifty-nine (159) sets of real-time environmental measurements consisting of one hundred and fifty-eight (158) in the school building and one (1) outdoors. All seven floors of the school were surveyed. These results are described below. Field data sheets are found in Attachment I.

Ke.'ipiritble P(ir/iciilciie.s (PM2, jj

Respirable particulate concentrations* indoors ranged between 8 ptg/m^ to 18 fig/m^ with an at crage of approximately 10 pg/mT All measurements were below the NPAAQS of 65 pg/mJ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentration was 24 ttg/m-T

CITY_21MC1OO_O11274315

NYC-WTC_OOO323932

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000323932Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →