Indoors air quality assessment report for Stuyvesant High School dated November 16, 2001.
13 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗ATC Associates indoor air quality assessment at a NYC school on Nov 16, 2001.
NYC-WTC_000323914–000323918OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan November 16, 2001 Indoor Air QiiaHty As.ses.sinent Page 3 Stuwe.sant I lich School (M477) ATC Project No.3 5-19125-0246
EKAkUMli K.nvironmental Measurements
ATC collected one hundred and si.vty-two (162) sets of real-time environmental measurements consisting of one hundred and sixty (160) in the school building and two f2) outdoors. All seven floors of the school were surveyed. These results are described below. Field data sheets are found in Attachment 1. Readings began at 8:30 P.M. and concluded after 4:15 P.M.
Teiiipeniturc
Indoor dry bulb temperature measurements ranged from 70.4 °F to 78.5 °F. Eighty-three (83) measurements were above the range of 68 to 75“F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). Tiiese measurements were collected throughout the school building. The outdoor temperature range was 60.4 and 76.2 °F.
Re/cirive Humidiiv
The relative humidity indoors ranged from 41.2 percent to 46.8 percent. All measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 43.2 to 52.8 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 539 ppm to 1116 ppm. All CO? measurements were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) COo concentration was 428 and 460 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1160 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of COo indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 0-1 ppm for all readings. These concentrations were below the NPAAQS/A.SHRAE guideline of 9 ppin. The outdoor CO concentration was 0-1 ppm-
Respirable Particulates (PMyj)
Respirable particulate concentrations* indoors ranged between 60 pg/mu to 120 jxg/m^ with an average of appro.ximately 77 gg/m-’. Only seven (7) measurements were below the NPAAQS of 65 pg/m-^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations were 124 and 148 pg/m^.
* fhe measurements made during this assessment were instantaneous readings, the guidelines are adopted from 24-hour and annual averages.
CITY_21MC1OO_OO3266823
NYC-WTC_000323916
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000312075
Indoors air quality assessment report for Stuyvesant High School dated November 16, 2001.
13 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000312094
ATC memo accompanying IAQ report for Stuyvesant High School, dated November 16, 2001.
12 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311814
ATC letter transmitting IAQ assessment results for Stuyvesant HS.
11 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311783
ATC IAQ assessment conducted at Stuyvesant High School for NYC BOE.
12 shared non-person entities · 1 shared topics · similarity 0.993
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311765
ATC IAQ assessment conducted at Stuyvesant High School for NYC BOE.
11 shared non-person entities · 1 shared topics · similarity 0.993
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000197518
Letter from ATC Associates reporting an indoor air quality assessment conducted at a Board of Education school in October 2001.
11 shared non-person entities · 1 shared topics · similarity 0.993
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311732
Indoor air quality assessment conducted October 12, 2001 at Stuyvesant High School.
11 shared non-person entities · 1 shared topics · similarity 0.993
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311979
Nov 7, 2001 memo documenting IAQ assessment at Stuyvesant High School.
13 shared non-person entities · 1 shared topics · similarity 0.993
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000293012
Indoor air quality assessment report for Stuyvesant High School dated Oct 29, 2001.
12 shared non-person entities · 1 shared topics · similarity 0.993
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000312163
ATC memo summarizing indoor air quality measurements at Stuyvesant High School, November 2001.
12 shared non-person entities · 1 shared topics · similarity 0.993
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000182669
Transmittal letter accompanying an indoor air quality assessment report for a Department of Education school conducted in October 2001.
12 shared non-person entities · 1 shared topics · similarity 0.993
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311704
Indoor air quality assessment conducted on October 10, 2001 at Stuyvesant High School.
12 shared non-person entities · 1 shared topics · similarity 0.993
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000197564
Letter from ATC Associates reporting an indoor air quality assessment conducted at a Board of Education school in November 2001.
Similarity score 0.990 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000197574
Letter from ATC Associates reporting indoor air quality measurements collected at a Board of Education school in November 2001.
Similarity score 0.989 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000312017
Nov 9, 2001 memo regarding IAQ assessment at Stuyvesant High School.
Similarity score 0.989 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000312163
ATC memo summarizing indoor air quality measurements at Stuyvesant High School, November 2001.
Similarity score 0.989 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000182883
Report of indoor air quality measurements collected at PS 234M on February 13, 2002, to assess acceptable air quality conditions.
Similarity score 0.989 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000330258
November 15, 2001 IAQ assessment report to NYC Board of Education.
Similarity score 0.989 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000312075
Indoors air quality assessment report for Stuyvesant High School dated November 16, 2001.
Similar indexed content
NYC-WTC_000312094
ATC memo accompanying IAQ report for Stuyvesant High School, dated November 16, 2001.
Similar indexed content
NYC-WTC_000311814
ATC letter transmitting IAQ assessment results for Stuyvesant HS.
Similar indexed content
NYC-WTC_000311783
ATC IAQ assessment conducted at Stuyvesant High School for NYC BOE.
Similar indexed content
NYC-WTC_000311765
ATC IAQ assessment conducted at Stuyvesant High School for NYC BOE.
Similar indexed content