Mr. Bernard P. Orlan April 23, 2002 Indoor Air Quality Assessment Page 3 P. S. 89M ATC Project No. 15-19125-0297 Real Time Environmental Measurements
ATC collected eighty (80) sets of real-time environmental measurements consisting of seventy (70) from inside the school building and ten (10) from outdoors. All five floors of the school building were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded at approximately 11:30 A.M.
Temperature
Indoor dry bulb temperature measurements ranged from 66.2 °F to 73.8 °F. Sixty-seven (67) of the indoor measurements for temperature were below and three (3) were within the range of 73 to 79°F (at 50 percent relative humidity) as recommended by the ASHRAF Standard 55-1992 during the summer season . The outdoor temperature measurements ranged from 50 °F to 52.6°F.
Relative Humidity
The relative humidity indoors ranged from 33.8 to 46.1 percent. All of the indoor measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 50 to 52.8 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 523 ppm to 1220 ppm. One (I) of the indoor measurements for CO2 was above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 465 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1165 ppm (background level + 700 ppm). The highest concentration was detected in room # 402 (1220 ppm) at 10:00 AM with 32 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant respiration. The school building was occupied during ATC’s assessment.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors was 1 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 1 ppm for all collected readings.
Respirable Particulates (PM2,$)
Respirable particulate concentrations* indoors ranged between 7 pg/m^ to 20 ug/m^. The average PM2.5 concentration for the entire school building was approximately 13 g/m^. All of the indoor and outdoor measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. Tlie outdoor respirable particulate concentration measurements ranged from 18 to 25 pg/m^ with an average of 21 pg inC
CITY_21MC100_003047602
NYC-WTC_000313522
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000369813
IAQ measurements collected at PS 89M for BOE; May 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000313685
IAQ measurements at PS 89M for May 17, 2002, per BOE request.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000313589
Indoor air quality measurements collected at PS 89M for BOE.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000369138
Indoor air quality measurements collected at P.S. 89M in May 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000313667
ATC measurements for PS 89M on May 15, 2002, temperature and humidity.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394453
IAQ measurements collected April 22, 2002 for P.S. 89M.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000392666
IAQ measurements report dated April 23, 2002 for PS 89M; BOE evaluation.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000210980
Report of indoor air quality measurements conducted at P.S. 89M on May 16, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000392864
ATC report of IAQ measurements at PS 89M requested by BOE.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000392756
ATC report detailing indoor air quality measurements at the referenced school.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370049
ATC IAQ measurements conducted June 14, 2002 for BOE air quality evaluation.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000199031
Cover letter from ATC Associates submitting indoor air quality measurement results for PS89M collected on June 14, 2002.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000222495
ATC Associates letter submitting indoor air quality measurement results collected on April 19, 2002, at P.S. 89M for the NYC Board of Education.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000313593
ATC measures temperature and basic IAQ parameters at PS 89M for BOE in May 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000392768
ATC report of IAQ measurements collected May 3, 2002 at the school.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000392661
IAQ report dated April 22, 2002 for PS 89M; BOE evaluation requested.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000369723
ATC IAQ measurements at PS 89M for BOE, May 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370049
ATC IAQ measurements conducted June 14, 2002 for BOE air quality evaluation.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000369813
IAQ measurements collected at PS 89M for BOE; May 2002.
Similar indexed content
NYC-WTC_000313685
IAQ measurements at PS 89M for May 17, 2002, per BOE request.
Similar indexed content
NYC-WTC_000313589
Indoor air quality measurements collected at PS 89M for BOE.
Similar indexed content
NYC-WTC_000369138
Indoor air quality measurements collected at P.S. 89M in May 2002.
Similar indexed content
NYC-WTC_000313667
ATC measurements for PS 89M on May 15, 2002, temperature and humidity.
Similar indexed content