Mr. Bernard P. Orlan ’November 27. 2001 Indoor .A.ir Quality Assessment Page 3 Stiivvesant High School (M477') ATC Project No. 15-19125-0246
Rea l-Time Enn'IRONmental Measurements
ATC collected one hundred and twenty (120) sets of real-time environmental measurements consisting of one hundred and eighteen (118) in the school building and two (2) outdoors. All ten floors of the school were surveyed. These results are described below. Field data sheets are found in Attachment 1. Readings began at 9:00 A.M. and concluded after 3;30 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 68.0 °F to 77.6 °F. Eleven (11) measurements were above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). These measurements were collected throughout the school building. The outdoor temperature range was 56.7 to 65.0 °F.
Jjelalive Humidity
The relative humidity indoors ranged from 30.4 percent to 48.1 percent. All measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 31.7 and 39.4 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 540 ppm to 1950 ppm. Sixteen (16) CO? measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations were 449 ppm and 465 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1165 ppm (background level -I- 700 ppm). The highest reading, 1950 ppm, was in Room 125. Rooms with CO2 levels above the recommended maximum were found on tlie 1 st, 3''’^, 4th, 6^11, 7th and 9th floors. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 0-1 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 1 PPin.
Respirable Particulates CPM2,5)
Respirable particulate concentrations* indoors ranged between 15 pig/m^ to 52 p.g/mA All measurements were below the NPAAQS of 65 p.g/m3 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations were 36 and 43 ug/mA
Filters with a higher efficiency rating were installed on the HX'AC units that serve rooms on the 3'"'^, 4th, 6^1 and 7^1 floors (See Attachment !)• The PMo.s concentration range for those rooms
CITY_21MC100_003046118
NYC-WTC_000312229
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000312283
Letter reporting lAQ measurements at Stuyvesant High School.
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402116
March 1, 2002 IAQ measurements report for Stuyvesant High School.
13 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000312245
Ltr: indoor air quality measurements at Stuyvesant High School.
13 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000270014
ATC report of IAQ measurements collected March 12, 2002 at Stuyvesant High School for NYC BOE.
13 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402139
March 6, 2002 IAQ measurements report for Stuyvesant High School.
13 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406580
April 18, 2002 memo detailing IAQ measurements at Stuyvesant High School.
13 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336429
BoE IAQ measurements at Stuyvesant HS; March 12–13, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000372722
Indoor air quality measurements at Stuyvesant High School conducted April 18, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000312263
Cover letter for lAQ report at Stuyvesant High School.
13 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000312017
Nov 9, 2001 memo regarding IAQ assessment at Stuyvesant High School.
13 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402182
March 12, 2002 IAQ measurements report for Stuyvesant High School.
13 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000273926
IAQ measurements conducted December 2001 at Stuyvesant High School for environmental health.
13 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000271345
Letter from ATC to BOE about IAQ assessment at Stuyvesant High School, Nov 13, 2001.
Similarity score 0.993 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311819
ATC IAQ assessment report issued for Stuyvesant High School.
Similarity score 0.993 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000312075
Indoors air quality assessment report for Stuyvesant High School dated November 16, 2001.
Similarity score 0.993 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311292
ATC report of IAQ measurements at Stuyvesant High School (M477).
Similarity score 0.993 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271233
Indoor air quality field report for Stuyvesant High School dated Oct 30, 2001.
Similarity score 0.993 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000293037
IAQ assessment conducted at Stuyvesant High School on Oct 30, 2001.
Similarity score 0.993 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000312283
Letter reporting lAQ measurements at Stuyvesant High School.
Similar indexed content
March 1, 2002 IAQ measurements report for Stuyvesant High School.
Similar indexed content
NYC-WTC_000312245
Ltr: indoor air quality measurements at Stuyvesant High School.
Similar indexed content
NYC-WTC_000270014
ATC report of IAQ measurements collected March 12, 2002 at Stuyvesant High School for NYC BOE.
Similar indexed content
NYC-WTC_000402139
March 6, 2002 IAQ measurements report for Stuyvesant High School.
Similar indexed content