, Mr. Bernard P. Orlan October 22. 2001 Indoor Air Quality Assessment Page 3 Stuvvesant High School (M477) ATC ProiectNo. 15-19125-0246

SAMPLING RESULTS

Real-Time Environmental Measurements

ATC collected one hundred and one (101) sets of real-time environmental measurements consisting of ninety (99) in the school building and two (2) outdoors. These results are described below. Field data sheets are found in Attachment 1.

Teniperatiifs

Indoor dry bulb temperature measurements ranged from 70.1 °F to 78.4 °F. Nine (9) measurements were above the range of 69 to 76°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). These readings were on the pt, 2'"’'^, 4^1'“ and 5^^ floors. The outdoor temperature range was 54.1 to 67.4 °F.

Relative Humidity

The relative humidity indoors ranged from 33.1 percent to 43.6 percent. All measurements were within the ASHRAE's recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 31.2 to 54.8 percent.

Carboti Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 411 ppm to 2280 ppm. Eleven (11) COg measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) COg concentration was 420 ppm. Therefore, the acceptable level of CO2 at this location was 1120 ppm (background level + 700 ppm). Rooms with high COg levels were found on the Ht, 3^*^, 4th, 5th, 9th and 1 Ot^i floors. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO? indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 0 ppm.

Respirable Particulates

Respirable particulate concentrations indoors ranged between 13 (ug/m^ and 47 ug/m^. All concentrations were below the NPAAQS/ASHRAE guideline of 50 pig/m^ (annual average concentration of particulate matter 10 micrometers or less in aerodynamic diameter). The outdoor respirable particulate concentration range was 21 to 75 ug/nN.

CITY_21MC100_003045624

NYC-WTC_000311816

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000311816Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →