Mr. Bernard P. Grian October 19, 2001 Indoor Air Quality Assessment Page 3 Stuvvesant High School (M477) ATC Project No. 15-19125-0246
SAMPLING RESULTS
Real-Time Environmental Measurements
ATC collected one hundred and five (105) sets of real-time environmental measurements consisting of one hundred and three (103) in the school building and two (2) outdoors. These results are described below'. Field data sheets are found in Attachment 1.
Temperature
Indoor dry bulb temperature measurements ranged from 70.3 °F to 79.0 °F. Eight (8) measurements were above the range of 69 to 76°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). These readings were on the ist, 2'"'^, 4th, 5th and 6th floors. The outdoor temperature range was 51.4 to 60.9 °F.
Relative Humidity
The relative humidity indoors ranged from 24.0 percent to 45.1 percent. Seventy-four (74) measurements were below the ASHRAE’s recommended range of 30 to 60 percent for occupant comfort. These readings were collected throughout the school building. The outdoor relative humidity range was 24.0 to 48.0 percent.
Carbott Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 419 ppm to 2498 ppm. Ten (10) CO2 measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of- <700 ppm above the background level. The outdoor (background) CO2 concentration was 349 ppm. Therefore, the acceptable level of CO2 at this location was 1049 ppm (background level + 700 ppm). Rooms with high CO2 levels were found on the 2'’^, 3’’d, 4tlT 5th, 6th, 7th and lO^h floors. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 0-1 ppm for all readings. These concentrations were below' the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration w'as 0 ppm.
Respirable Particulates
Respirable particulate concentrations indoors ranged between 4 jag/m^ and 26 pg/m^. All concentrations were below' the NPAAQS/ASHRAE guideline of 50 pg/m3 (annual average concentration of particulate matter 10 micrometers or less in aerodynamic diameter). The outdoor respirable particulate concentration range was 9 to 1 4 pg/m^.
CITY_21MC100_003081634
NYC-WTC_000292938
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000271233
Indoor air quality field report for Stuyvesant High School dated Oct 30, 2001.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000292952
ATC IAQ assessment conducted at Stuyvesant High School, Oct 2001, for NYC Board of Education.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271149
Indoor air quality assessment conducted on Oct 18, 2001 at Stuyvesant HS.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271218
Indoor air quality field report for Stuyvesant High School dated Oct 29, 2001.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000292901
IAQ field report correspondence for Stuyvesant H.S. dated Oct 17, 2001.
11 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000292918
IAQ field report for Stuyvesant H.S. dated Oct 18, 2001.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271119
October 2001 IAQ assessment report for Stuyvesant High School.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000293037
IAQ assessment conducted at Stuyvesant High School on Oct 30, 2001.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000330258
November 15, 2001 IAQ assessment report to NYC Board of Education.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000182704
Cover letter from ATC Associates submitting an indoor air quality assessment report for Stuyvesant High School conducted on November 8, 2001.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271154
UAQ indoor air quality assessment report for Stuyvesant High School in Oct 2001.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000293103
Indoor air quality assessment conducted for Stuyvesant High School by ATC Associates.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000271119
October 2001 IAQ assessment report for Stuyvesant High School.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000292967
Indoor air quality assessment report for Stuyvesant High School dated Oct 22, 2001.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271169
Indoor air quality assessment report for Stuyvesant HS dated Oct 2001.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000293037
IAQ assessment conducted at Stuyvesant High School on Oct 30, 2001.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271233
Indoor air quality field report for Stuyvesant High School dated Oct 30, 2001.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000292987
Report of IAQ assessment conducted at Stuyvesant High School on Oct 26, 2001.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
Indoor air quality field report for Stuyvesant High School dated Oct 30, 2001.
Similar indexed content
NYC-WTC_000292952
ATC IAQ assessment conducted at Stuyvesant High School, Oct 2001, for NYC Board of Education.
Similar indexed content
NYC-WTC_000271149
Indoor air quality assessment conducted on Oct 18, 2001 at Stuyvesant HS.
Similar indexed content
NYC-WTC_000271218
Indoor air quality field report for Stuyvesant High School dated Oct 29, 2001.
Similar indexed content
NYC-WTC_000292901
IAQ field report correspondence for Stuyvesant H.S. dated Oct 17, 2001.
Similar indexed content