' Mr. Bernard P. Orlan October 22.2001 Indoor Air Quality' Assessment Page 2 Stuvvesant Hieh School ('M477) ATC Project No. 15-19125-0246
The assessment was performed consistent with generally accepted indoor air quality assessment practices. As with all such assessments, there were inherent limitations created by constraints of time, operational and work practice variability, variations in air contaminant concentrations, and sampling and analytical accuracy. The results of the sampling represent conditions found on the dates of the survey and may not represent conditions found at other times. The information presented in this report should be used by the Board of Education as a guide to assess the need for further improvements in current indoor air quality control activities.
EVALUATION CRITERIA
Currently, there are no regulatory standards for indoor air quality in non-industrial buildings, such as offices and schools. For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications:
Ventilation for Acceptable Indoor Air Quality (ASHRAE 62-1999), American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE); Tltertnal Environmental Conditions for Human Occupancy (ASHRAE 55-1992); Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA).
Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation. Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality will be achieved at all times.
TABLE 1 TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED
PARAMETER TARGETLEVEL AGENCY OR ORGANIZATION Carbon Dioxide <700 parts per million (ppm) ASHRAE 62 (CQ2)___________ above background level Carbon Monoxide 9 ppm USEPA NPAAQS (as cited in (CO) ASHRAE 62) Respirable 50 micrograms per cubic meter USEPA NPAAQS (as cited in Particulates (PMjo) of air (pg/m^) ASHRAE 62) Temperature Summer: 73-78.5°F at 50% RH ASHRAE 55 Winter; 69-76°F at 50% RH Relative Humidity 30-60 % ASHRAE 55 Total Volatile 1 ppm Organic Compounds AHA (TVOC) USEPA = United States Environmental Protection Agency NPAAQS = National Primary Ambient-Air Quality Standard AIHA = American Industrial Hygiene Association
CITY_21MC100_003045623
NYC-WTC_000311815
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000311783
ATC IAQ assessment conducted at Stuyvesant High School for NYC BOE.
12 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311765
ATC IAQ assessment conducted at Stuyvesant High School for NYC BOE.
11 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271149
Indoor air quality assessment conducted on Oct 18, 2001 at Stuyvesant HS.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271119
October 2001 IAQ assessment report for Stuyvesant High School.
11 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000293037
IAQ assessment conducted at Stuyvesant High School on Oct 30, 2001.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271154
UAQ indoor air quality assessment report for Stuyvesant High School in Oct 2001.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000292918
IAQ field report for Stuyvesant H.S. dated Oct 18, 2001.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311846
ATC letter enclosing IAQ assessment results for Stuyvesant HS.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000197518
Letter from ATC Associates reporting an indoor air quality assessment conducted at a Board of Education school in October 2001.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311979
Nov 7, 2001 memo documenting IAQ assessment at Stuyvesant High School.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000312017
Nov 9, 2001 memo regarding IAQ assessment at Stuyvesant High School.
12 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000197534
Letter from ATC Associates reporting an indoor air quality assessment conducted at a Board of Education school in October 2001.
12 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000271198
Indoor air quality assessment report for Stuyvesant High School.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271169
Indoor air quality assessment report for Stuyvesant HS dated Oct 2001.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000197534
Letter from ATC Associates reporting an indoor air quality assessment conducted at a Board of Education school in October 2001.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311903
ATC letter with IAQ assessment findings for Stuyvesant HS.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311922
ATC release of indoor air quality assessment results for Stuyvesant HS.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311998
Nov 8, 2001 memo re: IAQ assessment at Stuyvesant High School (M477).
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000311783
ATC IAQ assessment conducted at Stuyvesant High School for NYC BOE.
Similar indexed content
NYC-WTC_000311765
ATC IAQ assessment conducted at Stuyvesant High School for NYC BOE.
Similar indexed content
NYC-WTC_000271149
Indoor air quality assessment conducted on Oct 18, 2001 at Stuyvesant HS.
Similar indexed content
NYC-WTC_000271119
October 2001 IAQ assessment report for Stuyvesant High School.
Similar indexed content
NYC-WTC_000293037
IAQ assessment conducted at Stuyvesant High School on Oct 30, 2001.
Similar indexed content